USER MANUAL
STM 550 / EMSI
–
ENOCEAN MULTISENSOR FOR IOT APPLICATIONS
© 2020 EnOcean | www.enocean.com F-710-017, V1.0
STM 550 / EMSI User Manual | v1.3 | September 2020 | Page 69/97
9.5.21
ACCELERATION_THRESHOLD
If reduction of the reporting interval based on acceleration has been enabled then the ac-
celeration threshold is defined by ACCELERATION_THREHOLD register as shown in Figure
48 below.
Note that this threshold is also used for the wake-on-acceleration function as described in
chapter 3.5.
ACCELERATION _THRESHOLD
Bit 15
Bit 14
…
Bit 1
Bit 0
ACCELERATION THRESHOLD
Figure 48
–
ACCELERATION _THRESHOLD register
The encoding used by the ACCELERATION THRESHOLD bit field is shown in Table 33 below.
ACCELERATION THRESHOLD
Threshold
0b000000
Reserved (Do not use)
0b000001 (Default)
1/64 * Full scale
0b000010
2/64 * Full scale
…
0b111110
62/64 * Full scale
0b111111
63/64 * Full scale
Table 33
–
ACCELERATION THRESHOLD bit field encoding