Page 37 of 78 Article no.: 1080621023 2022_02_14 Subject to technical change! Errors excepted.
9 Application Conditions
SensoStar
Maximum flow qs/qp
2:1
Mechanical class
M2
Electromagnetic class
E2
Environmental class
C
Protection class flow sensor
IP65
Nominal pressure PN
bar 16
Mounting position
any, if there is no indication on type label
Flow sensor of
SensoStar E
and
SensoStar
multi-jet heat meters
Temperature range medium heat
°C
15 – 90
Temperature range medium cooling
°C
5 – 50 (qp 1,5 and qp 2,5)
Flow sensor of
SensoStar
U
Temperature range medium heat
°C
15 – 90
15 – 130 high temperature (150; for maximal 2000 h) (optional)
Temperature range medium cooling
°C
5 – 50 (from qp 1,5 to qp 10)
Temperature range medium
heat/cooling
°C
15 – 90 heat
15 – 120 high temperature (optional)
5 – 50 cooling
Calculator
Ambient temperature in the field
°C
5 – 55 at 95 % relative humidity
Transport temperature
°C
-25 – 70 (for maximal 168 h)
Storage temperature
°C
-25 – 55
Protection class
IP65
10 Interfaces and Options
10.1 Optical (infrared) interface
For communication with the optical interface an optocoupler and the “Device Monitor” software are necessary.
The optocoupler and “Device Monitor” are available as accessory equipment.
The optical infrared interface will be activated by automatically sending a header (according to EN 13757-3). Baud
rate: 2400 baud.
Then you can communicate with the meter for 4 seconds. After every valid communication the meter is open for
another 4 seconds. Afterwards the display is deactivated.
The number of read-outs per day via the optical interface is limited. During daily read-out at least 4
communications are possible. If read-outs are carried out more rarely, the possible number of communications will
increase.
10.2 Retrofitting with an additional communication interface (optional)
We also offer a retrofittable meter to which communication interfaces can be added later. You will find the
description of our optional interfaces in the operating instructions „Communication Interfaces S3(C)“.
To retrofit such a meter with an additional communication interface the calculator´s adhesive seal has to be
destroyed and the device´s calculator to be opened.
When the calculator is open please observe the ESD
requirements according to EN 61340-5-1.
Use a screwdriver with a wide tip (4 - 5 mm) and carefully press in the two round predetermined breaking points
above the cable feedthroughs (see picture 1).