BEFORE
START
‐
UP
Remove
tie
‐
down
bolts,
straps
and
blocks
on
fan
and
compressor
vibration
isolators,
tilt
equipped
heat
pipes
and
enthalpy/desiccant
wheels
if
supplied.
Perform
a
Safety
Shutoff
Valve
Leak
Test
as
described
in
this
manual.
START
‐
UP
CHECK
LIST
Warning:
This
unit
is
connected
to
high
voltages.
Electrical
shock
or
death
could
occur
if
instructions
are
not
followed.
This
equipment
contains
moving
parts
that
can
start
unexpectedly.
Injury
or
death
could
occur
if
instructions
are
not
followed.
All
work
should
be
performed
by
a
qualified
technician.
Always
disconnect
and
lock
out
power
before
servicing.
DO
NOT
bypass
any
interlock
or
safety
switches
under
any
circumstances.
The
start
‐
up
and
operation
must
be
in
accordance
with
safe
practices.
Start
‐
up
must
be
performed
by
qualified
personnel.
Complete
attached
start
‐
up
record.
1.
Set
all
associated
electrical
switches,
controls,
thermostats
and
main
disconnect
switch
to
“OFF”
position.
2.
Close
all
manual
valves
and
field
piping
valves.
3.
Confirm
that
all
shipping
materials
have
been
removed.
See
any
supplemental
instructions
shipped
with
the
unit
to
help
identify
possible
locations.
4.
Check
all
bearings,
drive
and
fan
set
screws
for
tightness.
5.
Turn
disconnect
switch
ON
(control
switch
is
still
off)
and
check
the
supply
voltage.
Voltage
must
be
within
10%
of
rating
plate.
If
not,
contact
the
installing
electrical
contractor
and
have
the
voltage
condition
corrected
before
continuing
start
‐
up.
6.
Check
all
fan
motors
for
correct
rotation.
If
incorrect,
reverse
rotation
on
incoming
power
only.
7.
Set
thermostat
or
controller
to
the
“OFF”
position
and
turn
unit
control
switch
“ON”.Check
the
amperage
draw
of
each
motor
and
compressor.
Refer
to
unit
or
motor
rating
plate
for
full
load
amps.
At
the
unit,
check
and
record
the
voltage
while
it
is
running.
For
3
phase
power
the
phase
to
phase
voltage
imbalance
should
be
less
than
2%.
A
2%
voltage
imbalance
can
cause
up
to
a
10%
current
imbalance
that
will
overheat
motor
windings.
To
calculate
voltage
imbalance
(NEMA
method)
refer
to
the
following
example:
Phase
to
phase
voltage
readings:
235V
236V
230V
The
average
Voltage
between
legs
is
233.7V
(235+236+230)/3
Highest
voltage
deviation
from
average
is:
233.7V
–
230V
=
3.7V
Voltage
imbalance
percentage
=
Highest
deviation
divided
by
average
X
100
3.7
/
233.7
x
100
=
1.6%
This
imbalance
is
less
than
2%
and
therefore
is
OK
If
voltage
imbalance
is
greater
than
two
percent
(2%),
turn
off
main
disconnect
and
contact
the
installing
electrical
contractor
to
have
the
voltage
condition
corrected.