The 

SA-025 

Programmable Timer Module is suitable for a wide range of timed security

and access control operations, such as door unlock timing, siren or bell timer, VCR timer,
and so on. Auto-sensing of input voltage and DIP switches for programming make
installation easy.

Features / Specifications:

• Timer can be set from 1 second to 60 minutes
• Can be triggered by applying or removing a positive or negative signal (+/-) or by

powering up the unit

• Relay can be programmed to activate at the start or at the end of the timing cycle
• Relay can also be set to activate for one second at the end of the timing cycle
• Relay can be programmed to pulse (flash) or be steady on
• Built-in reset function to manually reset timing cycle
• Form-C relay, contacts rated 8A @ 120VAC/24VDC
• LED indicates relay is energized
• 12VDC/24VDC operation (auto sensing)
• Current draw – Less than 1mA (standby) or 50mA (relay energized)
• Board measures 2-7/8” x 2-1/2” (73 x 63 mm)
• Functions programmed via DIP switches – no jumpers to cut

Fig. 1 – DIP switch settings

Switch

#1

#2

#3

#4

#5

#6

Off

Fixed 1 sec. Relay
output time

Output at END of
COUNTER

REPEAT timing cycle

Time in MINUTES

Timing controlled by
TRG input

Counter begin at START
of TRG

On

Variable Relay output
time

Output at START of
COUNTER

SINGLE timing cycle

Timing in SECONDS

Timing controlled by
Power Up

Counter begin at END
of TRG

ENFORCER

®

Installation Manual

SA-025

Programmable Timer Module

Wiring:

TRG

 – Positive (+) trigger signal input

TRG

 – Negative (-) trigger signal input

(1K ohm resistor required - included)

(-)

 – 

Ground input

(+)

 – +12VDC to +24VDC input

NO

 – Relay output (normally open)

COM

 – Relay output (common)

NC

 – Relay output (normally closed)

DIP Switch Settings (Programming):

The SA-025 is programmed via a series
of six DIP switches which can be turned
on or off. See fig. 1.

SECO-LARM

SECO-LARM

SECO-LARM

SECO-LARM

SECO-LARM

®

 U.S.A., Inc.

 U.S.A., Inc.

 U.S.A., Inc.

 U.S.A., Inc.

 U.S.A., Inc.

16842 Millikan Ave., Irvine, CA  92606

SECO-LARM's policy is one of continual development and improvement.  For this
reason, SECO-LARM reserves the right to change specifications without notice.
Copyright © 2003 

SECO-LARM

®

 U.S.A., Inc.

  All rights reserved.

file: MIA025_Newf.pmd Feb 2003

b.

Action

 – If the TRG terminal is connected to (+) momentarily, the relay output

immediately activates for about one second. To reset the SA-025, the TRG must be
disconnected from (+) for at least two seconds. The timer has no effect.

c.

Triggering by powering unit up

 – If DIP switch #5 is set to ON, the output works the

same, but instead of triggering via the TRG terminal, the SA-025 is triggered by being
powered up.

4.

Latched Output, delayed (Fig. 5):

a.

DIP

 switch settings:

1 – ON
2 – ON
3 – ON

4 – Timer setting (ON or OFF)
5 – OFF
6 – OFF

b.

Action

 – If the TRG terminal is connected to (+) for the time set by the timer, the

relay activates and remains activated. To reset the latched relay, connect the TRG
terminal momentarily to (+) again.

c.

Triggering by powering unit up

 – If DIP switch #5 is set to ON, the delay period set

by the timer starts when the  SA-025 is powered up.  At the end of the delay period,
the relay latches on and remains on until the SA-025 is disconnected from power.

5.

Pulsing or Flashing Output, instant or delay (Fig. 6)

:

a.

DIP

 switch settings:

1 – Relay output mode, see below
2 – Instant/delay start, see below
3 – OFF

4 – Timer setting (ON or OFF)
5 – OFF
6 – OFF

b.

Action

 – If the TRG terminal is connected to (+) momentarily, the SA-025 waits for

the time set by the timer, and then starts pulsing/flashing. The pulse/flash output lasts
until the TRG terminal is disconnected from (+).

c.

Triggering by powering unit up

 – If DIP switch #5 is set to ON, the output works the

same, but instead of triggering via the TRG terminal, the SA-025 is triggered by being
powering up.

d.

Instant/delay start

 – If DIP switch #2 is set to ON, the SA-025 waits for the time set

by the timer after triggered or powered up, and then starts pulsing/flashing. If DIP
switch #2 is set to OFF, the SA-025 starts pulsing/flashing as soon as it is triggered
or powered up.

e.

Relay output time

 – If DIP switch #1 is set to ON, the relay on and off time depends

on how the timer is set. If DIP switch #1 is set to OFF, the relay on time is fixed at
about 1 second, and the relay off time depends on how the timer is set.

6.

Optional Negative Trigger or Closed-Circuit Trigger (Fig. 7):

If a closed-circuit or negative trigger is required, it is necessary to install a 1K
(1,000-ohm) resistor as shown (included).