background image

Setting the Timer:

The relay output time can be programmed for either 1 to 60 seconds, or 1 to 60 minutes,
using the round, black thumbwheel:

1. Determine and set DIP switch #4 according to whether the timing should be measured

in seconds or minutes (see DIP Switch Settings above).

2. Turn the thumbwheel on the SA-025 clockwise to increase time, and counter-clockwise

to decrease time.

3. Test the time, and make adjustments as needed.
NOTE – You should carefully test the time period once it is set.

Sample Installations for Common Timer Applications:

NOTE – The following only represents a few of the many possible ways to use this Timer
Module.  For your specific application, it may be necessary to experiment with the DIP
switch settings.
1.

Momentary trigger, no delay

 (for timed annunciator or supervisory circuit)

 (Fig. 2):

a.

DIP

 switch settings:

1 – ON
2 – OFF

3 – ON
4 – Timer setting (ON or OFF)

b.

Action

 – If the TRG terminal is connected to (+) momentarily, the relay output

immediately turns on. The output stays on for the time set by the timer, after which it
turns off regardless of whether the trigger is connected or disconnected.

NOTE

 – If the momentary trigger time is less than the time set by the timer, the relay

output is triggered only once. If the trigger time is longer than the timer time, the relay
will be activated a second time when the trigger is removed.

c.

N.O. vs. N.C. output

 – For a timed door annunciator, connect a buzzer or chime to

the N.O. and COM outputs. For a closed-loop supervisory circuit, connect a dialer or
transmitter to the N.C. and COM outputs.

2.

Momentary trigger, no delay

 (for swinger eliminator)

 (Fig. 3):

a.

DIP

 switch settings:

1 – ON
2 – OFF

3 – ON
4 – Timer setting (ON or OFF)

b.

Action

 – If the TRG terminal is connected to (+) momentarily, the relay output

immediately turns on, and stays on for as long as the TRG terminal is connected to
(+). Once the TRG connection is broken, the relay output remain activated for as long
as the time period set by the timer, and then turns off.

c.

Triggering by powering unit up

 – If DIP switch #5 is set to ON, the output works the

same, but instead of triggering via the TRG terminal, the SA-025 is triggered by
powering it up. Once powered up, the relay remains activated for the time set by the
timer, or until power is removed, whichever comes first.

3.

One-time 1-sec. momentary trigger, no delay (Fig. 4):

a.

DIP

 switch settings:

5 – OFF
6 – OFF

5 – OFF
6 – ON

1 – OFF
2 – OFF

3 – ON
4 – Timer setting (ON or OFF)

5 – OFF
6 – ON

Fig. 2 – Momentary trigger, no delay

Fig. 7 – Optional negative or

closed-circuit trigger

Fig. 6 – Pulse/flash o/p, instant/delay

Fig. 5 – Latched output, delayed

Fig. 4 – 1-time mom. trigger, no delay

Fig. 3 – Momentary trigger, no delay

Note: regarding DIP switch #1:
Sometimes DIP switch #1 will function as an
instant/delay control, but when it is ON, its actual
function depends on how DIP switch #3 is set.

DIP #1 setting

Function

OFF

1-sec. momentary relay output

ON (DIP #3 ON)

Relay output latches on

ON (DIP #3 OFF) Relay output equals 1 sec.

*

*(1K ohm resistor included)

*

Reviews: