ENFORCER Room Occupancy Monitor
6
SECO-LARM U.S.A., Inc.
Installation Using Mounting Screws:
Wiring Using Screw Terminals:
Slide
down
1.
Remove the top cover and PCB. Place the bottom case on the wall
where it is to be mounted, and mark the wall through the two
mounting holes.
2.
Screw two mounting screws (not included) into the marked locations,
and slide the bottom case down onto the screws, see right.
3.
Tighten the screws as needed, but take care not to overtighten and
ensure the case can still be removed by sliding.
4.
Replace the top cover and slide back onto mounting screws.
1.
If needed, mark the location of the wire pass-through hole during
installation and drill a hole to run wires.
2.
Remove the bottom case and PCB and feed the wires through the
wire pass-through holes (PCB and case) and wire as indicated below.
3.
Replace the top cover and mount.
Wire
pass-through
Door N.O. input (DNO+)
GND
Service output
(SOP-)
V+ (5~12 VDC)
Service input, N.O. (SIP-)
Sensor
(RM-R100-TLQ)
V+ (5~12 VDC)
GND
2-Room Indicator
(RM-R100-R2Q)
GND
Service input, N.O. (SIP-)
V+ (5~12 VDC)
1-Room Indicator
(RM-R100-RB1Q)
Using a Magnetic Contact for Door Monitoring:
Sensor terminal block
100kD
DNO+
GND
SOP-
V+
SIP-
DNO+
GND
SOP-
V+
SIP-
N.O. Magnetic Contact
N.C. Magnetic Contact
•
Door monitoring should only be used
for applications where the door being
monitored is usually kept open.
•
If an N.C. magnetic contact is being
used to monitor the door then a 100kD
resistor (not included) should be
installed between the voltage and door
contact inputs.