34
9.3 About the introduction of ‘Custom Setting’ mode,
‘Test’ mode, and ‘60Hz’ mode
• ‘Custom Setting’ mode: Under common conditions, it is not used, and it is mainly used by some special
customer to know the grid situation. When it is in this mode, customer can set the upper and lower
limits of voltage and efficiency in a wide range to meet his requirements via software. Absolutely, it
is not modified randomly by customer because of the password protection, and we will provide the
password for customer.
• ‘Test’ is set for the problem of frequency fluctuation when it is aging, test as follows:
- (1) Before T1 test, dial safety switch under common conditions, namely, where the machine is where it dial to.
- (2) After T1 test, before aging, turn the switch to aging mode.
- (3) After aging, before T2 test, turn the switch to common condition.
• ‘60Hz’ mode is not used for the moment.
Note: The switch should be set before power up, or it become invalid.
9.4 About the introduction of different safety standards
in different countries on LCD
Press the button ‘Function’, enter into the menu, you can see different countries with different safety
standards. When switch respectively corresponds to Germany, Spain, Italy, 60Hz, UK, Belgium, Custom
Setting and Test, and the menu shows as follows:
9.5 Mains voltage, efficiency range and time reset
after disconnection
Country
reconnection
time (S)
Vmin (V)
Vmax (V)
Fmin (Hz)
Fmax
(Hz)
VDE0126 – Germany/France/Bulgaria
30
187
262
47.51
50.19
RD1663 – Spain
180
198
250
49.01
50.99
DK5940 – Italy
30
187
262
49.7
50.3
G83 – United Kingdom
180
209
262
47.01
50.49
Belgium – Belgium
30
198
253
47.5
50.5
Germany/France/Bulgaria
Spain
Italy
60Hz
United Kingdom
Belgium
Custom Setting
Test