34
Destination 1.5 Insert Installation and Operation Manual
In the case of a known
K
and thickness of alternative materials to be used in combination, convert
all
K
values to R by dividing the thickness of each material by its
K
value. Add the
R
values of your
proposed materials as shown in the previous example.
Example:
K value = 0.75
Thickness = 1
R value = Thickness/K = 1/0.75 = 1.33
Thermal Characteristics of Common Floor Protection Materials*
MATERIAL CONDUCTIVITY
(k)
PER INCH
RESISTANCE (R) PER INCH
THICKNESS
Micore
®
160
0.39
2.54
Micore
®
300
0.49
2.06
Durock
®
1.92
0.52
Hardibacker
®
1.95
0.51
Hardibacker
®
500
2.3
0.44
Wonderboard
®
3.23
0.31
Cement mortar
5.00
0.2
Common brick
5.00
0.2
Face brick
9.00
0.11
Marble
14.3 – 20.00
0.07 – 0.05
Ceramic tile
12.5
0.008
Concrete 1.050
0.950
Mineral wool insulation
0.320
3.120
Limestone 6.5
0.153
Ceramic board (Fibremax)
0.450
2.2
Horizontal still air** (1/8") 0.135
0,920**
* Information as reported by manufacturers and other resources
** For a 1/8" thickness. You cannot «stack» horizontal still air to accumulate R-values; you must separate each
layer of horizontal still air with another non-combustible material.