9
3916010 06.16
4.2 CONTINUOUS FAN OPERATION
For continuous fan operation, connect the fan to the control
as described below.
• Connect a 1x120 VAC power supply to terminals 1, 2 and 3
• Jump terminals 5 and 9.
• Jump terminals 6 and 8.
• Connect the appliance:
- Connect the start signal from the appliance to terminals
14 and 15.
• Connect the fan:
- If using a 1x120V fan, connect it to terminals 19, 20 and
21. Refer Fig. 7 and the fan’s Installation Manual.
- If using a 3-phase fan and VFD, connect the VFD to
terminals 25 and 26 as shown in Fig. 10 and 11.
DO NOT connect the fan directly to the MEC 18 control.
• Connect the transducer (XTP) to terminals 22, 23 and 24.
Fig. 7
MEC 18 Control Board
COM Vout Vin
Summary of Contents for MEC 18