159
Installation instructions for professionals
Location on MD
controller card
Voltage/current
Cable example
External wiring of
the ventilation unit
TE10 supply air temperature
(Dehum/Twin Tropic/TCG)
AI12
(program-defined)
0–10 VDC
KLM 4x0.8
Yes, if duct coil
Free
AI13
(program-defined)
0–10 VDC
KLM 4x0.8
Free
AI14
(program-defined)
0–10 VDC
KLM 4x0.8
Free
AI15
(program-defined)
0–10 VDC
KLM 4x0.8
Free
AI16
(program-defined)
0–10 VDC
KLM 4x0.8
Analog outputs (AO)
Cooling control voltage /
additional post-heating control
voltage (MDX-E/HP-E/HP-W)
AO3
0-10 VDC 10 mA
KLM 2x0.8
Yes, except if in-built
coil
Heating control voltage /
compressor power control
voltage (MDX/HP)
AO5
0-10 VDC 10 mA
KLM 2x0.8
Yes, if MDX or water
heating
Pre-heating control voltage /
pre-cooling control voltage
(CHG) / LTO n:o 2 control voltage
(Twin Tropic)
AO6
0-10 VDC 10 mA
KLM 2x0.8
Yes, CHG
Exhaust air pre-heating control
voltage (HP) / exhaust air drying
control voltage (TCG) / LTO
de-frosting control voltage
(WGHR)
AO7
0-10 VDC 10 mA
KLM 2x0.8
Yes, if duct heating
Hot water production control
voltage
AO8
0-10 VDC 10 mA
KLM 2x0.8
Yes
Digital inputs DI
Connected to
a potential-free
terminating
connector
Emergency stop
DI1 (fixed)
24 VDC
KLM 2x0.8
Yes
PDS10 supply air blower
pressure switch / de-frosting
indication (MDX/HP)
DI2 (user-defined)
24 VDC
KLM 2x0.8
Yes, MDX
Overtime (only in Office use)
DI3 (user-defined)
24 VDC
KLM 2x0.8
Yes
Manual boost
DI4 (user-defined)
24 VDC
KLM 2x0.8
Yes
Away mode
DI5 (user-defined)
24 VDC
KLM 2x0.8
Yes
Overpressure
DI6 (user-defined)
24 VDC
KLM 2x0.8
Yes
Central vacuum system
indication
DI7 (user-defined)
24 VDC
KLM 2x0.8
Yes
Cooker hood indication
DI8 (user-defined)
24 VDC
KLM 2x0.8
Yes
Electrical post-heating alarm /
compressor failure (MDX/HP)
DI10 (fixed)
24 VDC
KLM 2x0.8
Yes, if MDX
Other connections
Control panel connections
X27, X28
10 m cable
supplied with
the unit
Yes
Modbus-RTU
X26
Instrument cable
2x2x0,5
Yes
Ethernet
X19
Cat5
Yes
O3 ozone sensor (ION)
ICEA2000A unit
connector 11
0–10 VDC
KLM 4x0.8
Yes
Summary of Contents for Salla eAir
Page 20: ...20 9 13 15 11 10 14 Lisävaruste 1 2 min 12 ...
Page 46: ...46 ...
Page 49: ...49 Installationsanvisningar för yrkesfolk ...
Page 50: ...50 Salla eAir Installationsanvisningar för ventilationsaggregat Svenska ...
Page 68: ...68 9 13 15 11 10 14 Extra tillbehör 1 2 min 12 ...
Page 94: ...94 ...
Page 97: ...97 Installasjonsinstrukser for fagfolk ...
Page 98: ...98 Installeringsinstruksjoner for ventilasjonsenheten Norsk Salla eAir ...
Page 116: ...116 9 13 15 11 10 14 Ekstrautstyr 1 2 min 12 ...
Page 142: ...142 ...
Page 145: ...145 Installation instructions for professionals ...
Page 146: ...146 Salla eAir Installation instructions for the ventilation unit English ...
Page 164: ...164 9 13 15 11 10 14 Extra 1 2 min 12 ...
Page 190: ...190 ...
Page 193: ...193 ...
Page 200: ...200 ...
Page 201: ...201 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 202: ...202 ...
Page 206: ...206 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...
Page 207: ...207 Enervent Zehnder Oy Kipinätie 1 FI 06150 PORVOO Tel 358 207 528 800 enervent enervent com ...