86
The equipment includes moving parts (e.g., fans and the
motor and belt of the rotating heat exchanger) that wear
out in use. Due to normal wear and tear, these parts must
be replaced during the lifecycle of the equipment. The
normal operating life of the wear-out parts is determined
on the basis of the operating conditions and operating
time. As a result, no normal maintenance interval can be
specified for the wear-out parts.
Maintenance reminder
The control panel advises the user to conduct the periodic
maintenance. The maintenance reminder
FILS
will appear
on the control panel display when the maintenance
interval has elapsed.
Acknowledge the maintenance reminder by pressing any
key on the eWind panel for 5 seconds.
Filters
MAINTENANCE
M5 and F7 cassette filters are used in the ventilation unit.
The recommended maximum maintenance interval for
the cassette filter is 4 months.
The unit requires very little maintenance. Sufficient
maintenance usually includes the following tasks:
•
Filter replacement
•
Cleaning of the heat exchanger (in connection with
the cleaning of the ventilation ducts)
•
Cleaning of the fans (in connection with the cleaning
of the ventilation ducts)
•
Inspection of the condensation water discharge pipe
Cassette filters may be cleaned using compressed air,
which extends the maintenance interval to six (6) months
at the most.
supply filter
F7
extract filter M5
The image depicts the
right-handed unit.
Before you begin any maintenance work, switch
the power off by removing the plug from the
socket. Wait for two (2) minutes before you begin
the maintenance. Even though the power supply
to the unit has been switched off, the fans will
continue running and the electric coil will be hot
for a while.
DANGER
When you are performing maintenance work
on a part of the equipment, always check the
cleanliness and degree of wear of the other parts,
as well.
Watch the maintenance instruction video in the
Help Center on our website at www.enervent.com.
FOR YOUR INFORMATION
The compressed air must be dry and oil-free.
FOR YOUR INFORMATION
Summary of Contents for Pingvin XL eWind
Page 24: ...24 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 25: ...25 Ilmanvaihtolaitteen k ytt ja yll pito ohje...
Page 26: ...26 Pingvin XL eWind Drift och underh llsanvisningar f r ventilationsaggregatet Svenska...
Page 48: ...48 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 49: ...49 Drift och underh llsanvisningar f r ventilationsaggregatet...
Page 50: ...50 Pingvin XL eWind Drift och underh llsanvisningar f r ventilationsaggregatet Norsk...
Page 72: ...72 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 73: ...73 Drifts og vedlikeholdsinstrukser for ventilasjonsenheten...
Page 74: ...74 Pingvin XL eWind Operating and maintenance instructions for the ventilation unit English...
Page 96: ...96 2016 1254 2014 A A ENERGIA ENERGIJA ENERGY ENERGIE ENERGI PINGVIN XL A 47 dB 340 m3 h...
Page 97: ......
Page 98: ......
Page 99: ......