Alarm Description

Alarm
limit

Symptoms

Possible reason

Action

Notes

AL4

Supply fan 

failure.

No Supply air.

Supply air fan has stopped.

Repair or change the 

supply fan.

The unit will 

not start before 

the alarm 

condition has 

been removed 

and the alarm 

acknowledged 

by pressing 

any button on 

the operating 

panel.

AL5

Extract fan 

failure.

No Extract air.

Extract air fan has stopped.

Repair or change the 

extract fan.

AL6

Extract air 

cold.

+10 °C

Supply air cold.

Indoor temperature low.

Rise the in temperature.

The ventilation 

unit enters the 

malfunction 

status, which 

means that the 

extract air fan 

is at minimum 

speed and the 

supply air fan 

has stopped.

The alarm is 

automatically 

acknowledged 

after the fault 

condition is 

removed.

Extract air duct heat 

insulation insufficient.

Check the insulation 

of the ducts and add 

insulation if needed.

Ventilation unit service 

hatch is open.

Close the service hatch.

TE30 temperature sensor is 

faulty.

Repair or change the 

sensor.

AL7

Supply air 

hot.
Fire hazard.

+55 °C

Supply air hot.

Fire hazard.

Check for any heat 

sources.

The unit will 

not start before 

the alarm 

condition has 

been removed 

and the 

ventilation unit 

restarted.

Electrical after heater is 

malfunctioning.

Repair or replace the 

electrical after heater.

Water after heater valve 

actuator is malfunctioning.

Repair or replace the 

valve actuator.

TE10 temperature sensor is 

faulty.

Repair or replace the 

temperature sensor.

AL8

Electric after-

heater or 

pre-heater 

overheating.

Supply air hot.

Electric pre- or after-heater 

is not functioning:

•  Overheating protector has 

tripped. 

 

•  Supply air fan has stopped. 

•  Supply air filter is blocked.
•  Outside air grating is 

blocked.

•  Controller card of heater is 

broken.

•  Heater is broken.

 

Find out the reason 

for overheating and 

acknowledge the error 

message.
Find out reason / replace 

the fan.
Replace the filter.
Clean the grating. 
Remove possible 

mosquito net.
Replace the controller 

card.
Replace the heater.

Summary of Contents for eWind

Page 1: ...User instructions ENG 25 01 2016 Enervent eWind...

Page 2: ...2 Copyright Ensto Enervent 2016 Unauthorized copying and lending are prohibited Approvals and version history Revision Date Description of change Approved by 0 0 2016 01 25...

Page 3: ...Using ventilation in cold season 8 ENHANCED FEATURES 8 Information view 8 eWind Info list 8 Measurements view 9 eWind Measurements list 9 Service reminder view 9 Time to service 9 Settings view 10 ADJ...

Page 4: ...he primary function of the unit The unit is also used for recovering heat energy from extracted air Depending on the model it can be used for cooling supply air during summertime It can also be used f...

Page 5: ...ure display 3 Mode button 4 Eco button 5 Temperature button Button display Description Mode display Current use mode Temperature display Target supply air temperature Mode button Selection of use mode...

Page 6: ...ntilation unit runs normally in the Home mode To select 1 Press the Mode button to scroll to mode 2 The ventilation system adjusts itself to the new setting Home mode with boosted ventilation 3 When e...

Page 7: ...w the system to make slight changes to the defined temperature and ventilation values to save energy In Eco mode the system will not react to temperature changes as quickly as in normal mode but waits...

Page 8: ...you increase the risk of ice build up in your ventilation unit This risk is higher during extreme freezing out conditions and with high indoor humidity extensive shower use and lots of drying laundry...

Page 9: ...C TE45 ESW only Other models show 0 12 r7 Pre heated outside air temperature CHG AGH electrical pre heater C TE02 Only if equipped with CHG AGH or electrical pre heater 32 r8 Relative humidity of extr...

Page 10: ...supply air Ventilation is not sufficient If the ventilation is not sufficient 1 Make sure the filters are clean and do not need to be replaced If the filters are dirty replace them as instructed in c...

Page 11: ...The error code is visible in the display All units are stopped AB fault tolerant The error code flashes in the display in 2 second intervals The exhaust fan runs in minimum speed Service Text FILS is...

Page 12: ...der prompt FILS when the service period has expired Acknowledge the FILS service reminder after maintenance by pressing any button on the eWind operating panel for 5 seconds NOTE When performing a mai...

Page 13: ...e is switched off NOTE For LTR series units The power cuts off when the service hatch is opened 1 Open the service hatch 2 Remove the filter from the ventilation device 3 Remove the filter fabric from...

Page 14: ...angers NOTE Visit the HelpCenter on our webpage www enervent fi for videos showing the maintenance tasks To replace DANGER DANGER Turn off the ventilation unit by switching off the main power supply b...

Page 15: ...ating the exchanger Leave the holders on the heat exchanger 8 Loosen the U beam on one side of the heat exchanger by removing the screws under the U beam rubber gasket 9 Unscrew the hexagonal screw of...

Page 16: ...d Restart the pump Replace the motor or the belt Replace the actuator Find out why replace the fan The unit will not start before the alarm condition has been removed and the alarm acknowledged by pre...

Page 17: ...nit service hatch is open Close the service hatch TE30 temperature sensor is faulty Repair or change the sensor AL7 Supply air hot Fire hazard 55 C Supply air hot Fire hazard Check for any heat source...

Page 18: ...18...

Page 19: ...19 User instructions EN...

Page 20: ...sto com www enervent com Enervent eWind ECO C 3 sec 120 min Quick guide for user ENG Acknowledge the FILS service reminder after maintenance by pressing any button on the eWind operating panel for 5 s...

Reviews: