background image

 

 

6/14 

ASAC-1 

 

 

4

 

Adjustments 

350%

90%

80%

70%

60%

400%

300%

50%

100%

16s

8s

12s

10s

No

Soft Stop

450%

250%

6s

4s

2s

14s

20s

16

8

12

10

OFF

6

4

2

14

20

16

8

12

10

OFF

TRIP

RUN

ANY

ANY

FWD

FWD

6

4

2

5s

2s

15s

5s

OFF

15s

5s

2s

2s

15s

14

20

14244.C

1

2

3

7

8

6

5

4

 

 

 

Current Ramp 

Current Limit 

Motor Trip Class 

Motor FLC 

Soft Stop Time 

Excess Start Time 

Auxiliary Relay Function 

Phase Sequence Protection 

 

 

  

1  Current Ramp 

 

 

 

Select the initial start current (A) and ramp time (B). 

Current ramp starting extends the time soft starter takes to reach the 

current limit and is suitable for generator set supplies, loads requiring 

an extended start time or applications with extreme load variation 

between starts. 

The ramp time does not control the time the motor will take to reach 

full speed. 

Cur

rent

 

 

Time 

2  Current Limit 

 

 

 

Select the current limit (C). 

The current limit is the maximum level of current the soft starter will 

deliver to the motor during the soft start. 

Cur

rent

 

 

Time 

3  Motor Trip Class 

 

 

 

Select the trip class for motor overload protection. 

The trip class reflects the maximum time (in seconds) that the motor 

can run at locked rotor current.  The Motor Trip Class setting 

assumes a locked rotor current of 600%. 

 

 

 

Setting the motor trip class to "Off" disables motor overload 

protection. 

 

4  Motor FLC 

 

 

 

Configure the soft starter to match the motor's full load current (FLC). 

Configure according to the motor's nameplate current. Divide the 

motor's FLC by the soft starter's maximum current rating (on the soft 

starter's nameplate label). 

 

0

8

2

3

9

.A

INPUT RATING:

200-440VAC, 50/60Hz, 3PH

OUTPUT FLC:

xxAAC53b4-6:354, 30 kW @ 400V

AUXILIARY CONTACTS: 5A@ 250VAC/360VA, 5A @30VDC Resistive

WITHSTAND CURRENT: 5000ARMS, 600VAC max.

POWER CONTACTS:

#10 - #2AWG, 6 - 35 mm2(3-5 Nm, 2.2-3.7 lb-ft)

AUXILIARY CONTACTS: 20 - 16AWG, 0.75- 1.5 mm2(0.5 Nm, 4.5 lb-in)

Motor FLC

Soft starter FLC

 

Summary of Contents for ASAC-1 Series

Page 1: ...the use of non original spare parts Enertronica Santerno reserves the right to make any technical changes to this manual and to the device without prior notice If printing errors or similar are detected the corrections will be included in the new releases of the manual The information contained herein is the property of Enertronica Santerno and cannot be reproduced Enertronica Santerno enforces it...

Page 2: ...to mains voltage Only a qualified electrician should carry out the electrical installation Improper installation of the motor or the soft starter may cause equipment failure serious injury or death Follow this manual and local electrical safety codes GROUNDING AND BRANCH CIRCUIT PROTECTION It is the responsibility of the user or person installing the ASAC 1 to provide proper grounding and branch c...

Page 3: ...1 090 200 160 240 216 214 114 5 51 6 5 ASAC 1 110 7 87 6 30 9 44 8 50 8 43 4 5 2 0 14 33 2 2 Physical Installation 1 ASAC 1 007 ASAC 1 055 Allow 100 mm 3 9 inch between soft starters ASAC 1 075 ASAC 1 110 Allow 200 mm 7 9 inch between soft starters 2 ASAC 1 007 ASAC 1 055 Allow 50 mm 2 0 inch between the soft starter and solid surfaces ASAC 1 075 ASAC 1 110 Allow 200 mm 7 9 inch between the soft s...

Page 4: ... x 2 24 VAC VDC A1 A2 WARNING Always apply control voltage before or with mains voltage CAUTION With 24 VAC VDC use contacts rated for low voltage and low current gold flash or similar 3 3 Control Circuits WARNING Isolate the ASAC 1 completely from the power supply before attempting any work on the ASAC 1 or motor Control terminals may be at phase voltage potential CAUTION For ASAC 1 xxx x 2 24 VA...

Page 5: ...grammable output relay terminals 23 24 can be used to signal either trip or run status This relay is normally open Trip The relay closes when the ASAC 1 trips The relay can be used to operate the shunt trip mechanism of an upstream circuit breaker in order to isolate the motor branch circuit or to signal the trip to an automation system or externally The relay will open when the trip is reset Run ...

Page 6: ... the current limit C The current limit is the maximum level of current the soft starter will deliver to the motor during the soft start Current Time 3 Motor Trip Class Select the trip class for motor overload protection The trip class reflects the maximum time in seconds that the motor can run at locked rotor current The Motor Trip Class setting assumes a locked rotor current of 600 Setting the mo...

Page 7: ... time E Current Time 7 Auxiliary Relay Function Select the function of the soft starter s programmable output terminals 23 24 When set to Run the relay will operate when the soft start is complete When set to Trip the relay will operate when the soft starter trips Time 8 Phase Sequence Protection Configure the soft starter s phase sequence protection Select the allowable phase sequences A setting ...

Page 8: ...on 5 3 Protections The ASAC 1 includes the following types of protection for the motor and starter 5 3 1 Excess Start Time Protection The ASAC 1 will trip on excess start time if the motor does not successfully start within the time selected in the Excess Start Time setting This may indicate that the load has stalled If the soft starter frequently trips on excess start time check that the Current ...

Page 9: ...s while running 5 3 5 Bypass Overload Protection Bypass overload protection protects the soft starter from severe operating overloads while running The protection is not adjustable and has two components The soft starter will trip if it detects overcurrent at 600 of the programmed motor full load current The soft starter models the temperature of the internal bypass relays and will trip if the tem...

Page 10: ...AC 1 soft starters support network communication via easy to install communications modules Each soft starter can support one communications module at a time Available protocols Ethernet Profinet Modbus TCP Ethernet IP Profibus DeviceNet Modbus RTU and USB NOTE Ethernet communication modules are not suitable for use with ASAC starters using 380 440 VAC control voltage 6 4 PC Software The software ...

Page 11: ...mage to SCRs from transient overload currents and for Type 2 coordination ASAC 1 soft starters have been tested to achieve Type 2 coordination with semiconductor fuses Suitable Bussmann and Ferraz Mersen semiconductor fuses are detailed below Model SCR I2t A2s Ferraz Mersen Fuse European IEC Style North American Style Bussmann Fuse Square Body 170M Bussmann Fuse British Style BS88 ASAC 1 007 1150 ...

Page 12: ...ion IEC 60068 Test Fc Sinusoidal 4 Hz to 13 2 Hz 1 mm displacement 13 2 Hz to 200 Hz 0 7 g EMC Emission Equipment class EMC Class B Conducted radio frequency emission 0 15 MHz to 0 5 MHz 56 46 dB µV 0 5 MHz to 5 MHz 46 dB µV 5 MHz to 30 MHz 50 dB µV Radiated radio frequency emission 30 MHz to 230 MHz 30 dB µV m 230 MHz to 1000 MHz 37 dB µV m EMC Immunity Electrostatic discharge 4 kV contact discha...

Page 13: ...ASAC 1 13 14 7 4 Model Code ASAC 1 Control voltage 1 110 240 VAC 380 440 VAC 2 24 VAC VDC Mains voltage 4 200 440 VAC 5 200 575 VAC Nominal kW rating 400 VAC 007 030 AC53b 4 6 354 037 110 AC53b 4 6 594 ...

Page 14: ...14 14 ASAC 1 ...

Reviews: