7.Test Running

7.1  Key check project before test running

● Set all the terminal screws tight before running.
● Check all the connection of the terminal.
● Make sure no short circuit phenomenon.

7.2 Test running method

According to “Installation Guide”,make COM1 and WH short circuit;The system situation and 
the light as follow table:

NO.

Light

System Situation

1

All the lights flash once

Power on

2

“POWER”light is on

System starts to self-check

3

“POWER + MPPT”light on

Pump starts to run

Remark

1

If water level sensors are not used,make COM1 and WH short circuit to run the 

system.

8.Maintanance Method

8.1 Regular maintanance project

● Every panel’s output voltage is in normal range.
● The tightness of terminal screws.
● Check if there are any dust/iron scrap/mordant liquidin controller.
● Check if there are any noise or shaking of the pump when the system is on.

8.2   Attentions during the maintanance

●Disconnect the input power of controller before maintanance;
●The demounted metal spare parts are not allowed to put into controller,it will lead to open-

circuit of controller;

●Keep  the  controller  clean  after  maintanance,avoid  any  dust  or  liquid  invade  into  the 

controller.

9. ERROR CODE AND MEANING

E001: Current Protection

E002

Voltage Protection

E003

Voltage Protection 

E004: Tank Protection

E005: Tank Protection

E006: Tank Protection

E007: Tank Protection

E008: Low level Protection

E009: Low level+Current Protection

E010: Low level+Voltage Protection

E011: Low level+Voltage Protection

E012: Tank+Low level Protection

E013: Tank+Low level+Current Protection

E014: Tank+Low level+Voltage Protection

E015: Tank+Low level+Voltage Protection

E016: Data error

E032: Verify and Error

E064: Communications Blackout

11

12