enertik BSSC4-29-1000-110V Manual Download Page 2

1.Safety

1.1    Before Power On

●Make  sure  the  terminal  wire  connections  are  correct,“P+”

“P-”are  for 

panel  connection,“1”

“2”

“3”for  pump  connection,wrong  connection  will 

lead to controller damage.

●The  voltage  of  panel  system  is  not  allowed  to  exceed  the  open-circuit 
voltage  of  controller  ,  avoid  to  use  same  power  supply  with  strong 
interference equipment , otherwise it will damage the controller.
●Match correct pump power with controller.
●Ensure  the  insulation  of  MOSFET  and  aluminum  board  during  the 
installation.

1.2   In running 

●When  the  system  is  running,it  is  not  allowed  to  disconnect  the  connection 
between pump and controller,other wise it may damage the pump motor and 
controller. 

●When the system is running,do not tough or exam the The parts of the circuit 
board or signal.
●Do not tough the radiator or any heat parts,in case of burns.  
●Unprofessinal operators are not allowed to operate or exam the controller.

2

.

Technical Specification

Table 1 Specification

150V

220V

300V

Rated Voltage

150VDC

220VDC

300VDC

Rated Current

10A

10A

10A

Max working Current

12A

12A

12A

Min working Current

1.3A

1.3A

1.3A

Open circuit voltage input

>170VDC

>272VDC

>340VDC

Open circuit voltage Max

250VDC

350VDC

450VDC

Open circuit voltage Min

90VDC

150VDC

220VDC

Max Power

1.5KW

2.2KW

3KW

Current

Overload

15±0.5A

15±0.5A

15±0.5A

Over current

32±0.5A

32±0.5A

32±0.5A

  Model

Specification

3.Protect Function Manual

Table 2 Protect Function Instruction

Protection

Manual

Protection of opposite 

connection

Solar Panel “PV+”“PV-”polarity are opposite connected, controller can 
continue working after adjust.

Load over current and short 

circuit protection

If the load current is more than15A and longer than 10s,the controller will 
be in protection mode; If more than 32±0.5A,the controller will stop 
working immediately. Try to re-start the controller 15mins later.

Weak Power Protection

Details See Table 4

50V: The working current smaller than 1.3A;Solar Panel input voltage 
smaller than 60VDC or bigger than 250VDC

Come into Protection mode. 

Try to re-start the controller 6mins later.
220V: The working current smaller than 1.3A;Solar Panel input voltage 
smaller than 110VDC or bigger than 350VDC

Come into Protection 

mode. Try to re-start the controller 6mins later.  
300V: The working current smaller than 1.3A;Solar Panel input voltage 
smaller than 220VDC or bigger than 450VDC

Come into Protection 

mode. Try to re-start the controller 6mins later.