enertexbayern Enertex KNXnet/IP Router Manual And Configuration Download Page 6

1150-HB-KNXnetIP-Interface-en-1.odt, 2018-08-06                                             

Seite 6 von 6 

tunnel [1..5]

Show tunnel addresses and connection status (without option), or show detailled information 

for a specific tunnel (option 1..5) 

CCID: connection id of the tunnel connection

KNX address: tunnel address

HPAI control: control-end-point of the receiver

HPAI data: data-end-point of the receiver

Connect. Type: tunnel connection or management connection

TX tun req: number of telegrams sent to this tunnel

TX tun re-req: number of telegrams that had to be repeated for this tunnel connection

RX tun req: number of telegrams received from this tunnel

RX tun re-req: number of telegrams that have been received twice for this tunnel connection

RX tun req (wrong seq.): number of telegrams with wrong sequence number that have been 

received for this tunnel

version

Show firmware version

Reset to factory defaults

To reset the device to factory defaults, press and hold the programming mode button for three 

seconds. When the red LED starts blinking release the button. The device shuts down and will 
reboot with factory settings automatically.

ETS database

You can download the latest version of the product's ETS database from our homepage:

http://www.enertex.de/e-downloads01.php

Technical data

Stromversorgung

16-24 V AC or 20-30 V DC; IEEE 802.3af („Power over Ethernet“)

Power consumption

Max. 1 W

KNX Funktionen        

KNXnet/IP tunneling

KNXnet/IP Tunnelling                       

Up to 35 telegrams per second, up to five tunnel connections

Enertex

®

 Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - Deutschland - [email protected]