Telnetserver
A integrated Telnet server provides additional functionalities. The default password for Telnet ac-
cess is „knxnetip“.
factory_reset
Reset the device to factory default and restart
ifconfig
Show IP settings
Sys multicast: multicast address for system telegrams
RT multicast: multicast address for routing telegrams
logout
Close Telnet session
passwd oldpw newpw
passwd oldpw
passwd newpw
Change Telnet passwort (
passwd old new
),
Delete passwort (
passwd old
)
Set passwort, if no password is set already (
passwd new
)
progmode [0|1]
Show programming mode status (without option) or set programming mode (
0
= off,
1
= on)
reboot
Restart device
stats
Show statistics
uptime: uptime since last reboot
TX to IP (all): number of telegrams sent to IP
TX to KNX: number of telegrams sent to KNX bus
RX from KNX: number of telegrams received from KNX bus
Overflow to IP: number of telegrams, that couldn't be sent to IP
Overflow to KNX: number of telegrams, that couldn't be sent to KNX bus
TX tunnel re-req: number of telegrams, that had to be repeated during tunnel access
tpconfig
Show KNX parameters
KNX bus state: KNX bus detected (up) or not detected (down)
KNX address: physical address of the device
Serial number: serial number of the device
tunaddr 1..5 address
tunaddr reset
Change tunnel address for each tunnel e.g.
tunaddr 1 15.15.240
or reset tunnel
addresses to factory default (
tunaddr reset
)