23
HP IOM, Rev. B
Enertech Global
Section 7: Controls
CONDITION
GREEN
HP
ORANGE
LP
RED
FS
YELLOW
CO
STATUS
GREEN L TERMINAL
1
NORMAL MODE
FLASH
TEST MODE
2
HP FAULT
FLASH
FLASH
HP LOCKOUT
ON
FLASH
ON
LP FAULT
FLASH
FLASH
LP LOCKOUT
ON
FLASH
ON
SOURCE COIL FRZ/ WF FAULT (T4/FS)
3
FLASH
FLASH
SOURCE COIL FRZ/ WF LOCKOUT (T4/FS)
3
ON
FLASH
ON
LOAD/ AIR COIL FRZ FAULT (T1)
4,5
FLASH
FLASH
FLASH
LOAD/ AIR COIL FRZ LOCKOUT (T1)
4,5
ON
ON
FLASH
ON
CO FAULT
5
FLASH
FLASH
CO LOCKOUT
5
ON
FLASH
ON
O/ U VOLTAGE
FLASH
FLASH
FLASH
FLASH
FLASH
ON
T1 FAULTY
5,6
FLASH
ON
FLASH
FLASH
T2 FAULTY
5,6
FLASH
ON
FLASH
FLASH
T3 FAULTY
5,6
FLASH
ON
FLASH
FLASH
T4 FAULTY
5,6
ON
FLASH
FLASH
FLASH
T1 & T4 SWAPPED
7
ON
ON
FLASH
HOT GAS LINE FAULT > 220F (T2)
8
FLASH
FLASH
ON
FLASH
HOT GAS LINE LOCKOUT > 220F (T2)
8
ON
ON
ON
FLASH
ON
JUMPER
FS
A‐FRZ
TEST
O/ V
NOTES:
2. WHEN THE TEST JUMPER IS PULLED, GREEN STATUS LED WILL BE OFF.
5. NOT ALL MODELS HAVE THIS FEATURE.
6. THIS FAULT INDICATES A BAD SENSOR (OPEN, SHORTED, OR DISCONNECTED).
7. THIS CAN ONLY BE CHECKED WHILE IN TEST MODE.
8. HOT GAS LINE IS TOO HOT.
OPEN LOOP MODE‐ 30F SETTING FOR
T4
CLOSED LOOP MODE‐ 15F SETTING FOR T4
LOCKOUT BOARD LED IDENTIFICATION & L TERMINAL STATUS
LOCKOUT BOARD JUMPERS
INSTALLED
REMOVED
T1 & T4 MONITORED FOR FLOW‐ 'FS'
TERMINALS IGNORED
FS' TERMINALS USED FOR FLOW SWITCH‐ T1
& T4 IGNORED
REV A. 03/25/16
4. THE LOAD/ AIR COIL FREEZE PROTECTION SENSOR IS LOCATED BETWEEN THE TXV AND LOAD/ AIR COIL.
OPERATES IN NORMAL MODE WITH
STANDARD DELAYS
OPERATES IN TEST MODE WITH DELAYS
SPED UP
FEATURE IS ACTIVE
FEATURE IS INACTIVE
1. THE 'L' TERMINAL CONTROLS A FAULT LED AT THE THERMOSTAT OR DRIVES AN AUXILIARY FAULT RELAY.
3. DEPENDING UPON MODEL, THE SOURCE COIL FRZ/ WATER FLOW FAULT OR LOCKOUT CAN BE AN INTERNAL OR EXTERNAL FLOW
SWITCH (FS), OR A SENSOR (T4) LOCATED BETWEEEN THE TXV AND SOURCE COIL.
Lockout Board LED Identification Table