The ambient temperature of the gas relay is too high

Heat insulate, max. 60° C.

The ignition spark is too weak

Check the transformer

Bad combustion

Bad draught conditions

Check the chimney

The lue gas temperature is too high

The boiler is overloaded. Reduce the quantity of gas.

The CO

2

-content is too low

Check the boiler with regard to leaks. Choke the draught  
if it is too high.

The CO-content is too high

Excess air when using natural gas and gasoil 
(propane, butane

Choke the air.

Air shortage

Open the air supply. Check the lue gas damper.

The holes in the gas nozzle are clogged

Clean.

The fresh air intake is too small

Check and enlarge.

The lame is not burning straight because the burner 

head is out of position

Check the burner head and readjust.

Condensation in boiler and chimney

The low gas temperature is too low or the quantity 

of gas is not suficient

Increase the lue gas temperature by increasing the  

gas supply. Insulate the chimney

REMEDY

CAUSE

4(4)

927

ø

2

3

0

A

ø

1

9

9

820

4

0

3

5

1

3

7

8

1

4

0

3

413

Capacity chart according 
to EN 676

Out range

TECHNICAL DATA

1

)  Caloriic value:

 

Natural gas 10 kWh/Nm

3

  

 LPG 26 kWh/Nm

3

    

 

The above dimensions are max. measurements. Depending on the compo-
nents used, the measurements may vary.

172 215 46  07-01

Type designation BG 700

Dimensions

Approved natural gas

Approved LPG

Length of burner  

tube ± 5 mm

Flange  

Measure A ± 5 mm

Standard

363

328

Long design

663

628

Type

Capacity 

kW

Gas volume at a min. 

output  Nm

3

/h  

1

)

Gas volume at a max 

output Nm

3

/h 

1

)

Max. inlet 

pressure mbar 

3

)

Natural gas

LPG

Natural gas

LPG

Natural gas

LPG

700

300-1500

360-1650

30

13,8

150

62,5

100-360

Rated inlet pressure 

mbar 

2

)

Connection  

2

)

Motor

Ignition transformer

Natural gas

50

LPG

50

Natural gas,LPG 

2½",  1½"

3,0 kW, 2800 r/m 

230/400 V 

11,2/6,5A

Primary 230 V, 1 A

Secondary 8 000 V

2

)  Dimension and capacity depen- 

 ding on gas quality and available  
 inlet  pressure

3

)  See data plate on the built-on

   (gas ittings) 

Summary of Contents for BG 700-2

Page 1: ...178 001 80 Installation and maintenance instruction BG 700 2...

Page 2: ......

Page 3: ...p is installed before servicing Take great care when servicing Trap and pinch risks can be present The boiler s sound level can exceed 85 dBA during operation Use ear protectors when present in the bo...

Page 4: ...eclare under our sole responsibility that the product name type or model batch or serial number possibly sources and number of items BG100 BG150 BG200 STG120 STG146 BG300 BG300LN BG400 BG400LN BG450 B...

Page 5: ...s not suficient Increase the lue gas temperature by increasing the gas supply Insulate the chimney REMEDY CAUSE 4 4 927 230 A 199 820 403 513 781 403 413 Capacity chart according to EN 676 Out range T...

Page 6: ...sations at start The ignition electrodes are wrongly adjusted Readjust The gas pressure is too high Check and adjust by means of a pressure gauge and a pressure adjustment valve The lue gas side is bl...

Page 7: ...relay defective Replace Air pressure switch incorrectly adjusted or defective Check the adjustment and readjust No reponse as the cams of the servomotor are not correctly adjusted or out of position T...

Page 8: ...nly be ensured by the correct combined effect of the three factors electricity gas low and combustion air Should any of these factors change troubles may arise It has been proved that many troubles ha...

Page 9: ...ity gasandair supply Should there be any changes intheratiobetweenthesethreefactors there is a risk of break downs It has been proved that most break downs are caused by simple faults Before callingth...

Page 10: ...e reason for a low ionisation current may be leaking currents bad connec tion to earth dirt or a faulty position of the lame electrode in the burner head Sometimes also a faulty gas air mixturemaycaus...

Page 11: ...ner is converted to ire another gas quality it must be re commissioned If town gas is to be ired the combustion head must be converted and the gas train adjusted to suit e g a larger gas armature or a...

Page 12: ...nd the motor will be dead Remove the link from the gas pressure switch after the test is inished 172 205 34 07 01 Leakage control Gas train Noteon2 stageandmodulatingburn ers that during the pre purgi...

Page 13: ...ipple inlet pressure 11 Test nipple pressure after governor 12 Test nipple before governor 13 Filter Max inlet pressure 360 mbar Adjustable governor pressure 405 412 S50 4 50 mbar 415 420 S20 4 20 mba...

Page 14: ...formation please contact the gas distributor 172 305 54 08 01 FUNCTION 2 STAGE DESIGN Air adjustment The damper motor turns the damper between three pre set positions fully closed low load full load T...

Reviews: