CONTROL PROGRAMME UNDER
FAULT CONDITIONS AND LOCK-
OUT INDICATION

In the event of fault conditions the
sequence switch stops and simul-
taneosly the lock-out indicator. The
symbol appearing above the reading
mark indicates kind of fault:

No start,

 because e.g., the CLOSE

signal has not been supplied to
terminal 8 by the limit switch, or a
contact has not been closed
between terminals 4 and 5.

Shut-down of start-up sequence,

because the OPEN signal has not
been supplied to terminal 8 by the
limit switch. Terminals 6, 7 and 15
remain under voltage until the fault
is corrected.

Lock-out

 due to a fault in the super-

vision circuit.

Shut-down of start-up sequence,

because the position signal for the
low-flame position has not been
supplied to terminal 8 by the
auxiliary switch. Terminals 6, 7
and 15 remain under voltage until
the fault is corrected.

Lock-out,

 because no flame signal

has been received on completion of
the saftey time.

Lock-out, 

because the flame signal

has been lost during burner
operation or air pressure failure has
occurred.

Lock-out on completion or after
completion of control pro-
gramme sequence

 due to

extraneous light (e.g. flame not
extinguished, leaking fuel valves)
or due to a faulty flame signal (e.g.
fault in flame supervision circuit or
similar).

a - b
Start-up sequence
b - b´
"idle steps"
up to the self shut-down of the sequence
switch
b ( b´) - a
Post-purge sequence

171 425 36  00-01

ELECTRIC EQUIPMENT

OIL BURNER CONTROL: LAL3...

FUNCTION

1.

Switch on operating switch and twin thermostat
The burner motor starts, an ignition spark is formed, the prepurge goes
on till the prepurge period expires and the solenoid valve 1 opens (2).

2.

Solenoid valve 1 opens
Oil mist is formed and ignited. The photocell indicates a flame.

3

The safety time expires
a. If there is no flame established 

before

 this time limit the burner

control locks out.

b. If the flame for some reason disappears 

after

 this time limit the

burner control also locks out. If a repetition of the start-up sequence
is desired, the wire link marked "Repetition" on the side of the base
plate of th control must be removed.

4.

Full load thermostat ON
The ignition spark goes out 2 s after flame indication when the ignition
transformer is connected to terminal 7. The burner is in operating
position and can now change between high and low capacity.

5.

Operating position
If the burner operation is interrupted by means of the main switch or the
thermostat, a new start takes place when the conditions in accordance
with point 1 are fulfilled.

The control locks out
A red lamp in the control is lit. Move the transparent cover aside and
restart the burner by pressing the reset button.

Note! In the window of the control symbols appear showing in which
position the control locks out , see the adjoining explanation.

TECHNICAL DATA

Pre-ignition time:

from start

Pre-purge time with full air volume:

22 s

Safety time:

5 s

Post-ignition time:

15 s

Interval between Mv1 and Mv2:

7,5 s

Reset after lock-out:

Immediately

Time of re-start:

47  s

Ambient temperature:

-  20  to + 60°C

Min. required current at 220 V and 240 V respectively:

95/105  µ A

Max. current:

160  µ A

Protective standard:

IP40

a

b

Summary of Contents for Bentone B60-2FH

Page 1: ...Providing sustainable energy solutions worldwide 178 039 61 2 2016 11 28 Installation and maintenance instruction B60 2FH...

Page 2: ......

Page 3: ...ing lamp Stage 2 13 Cover inspectionglass 14 Indicating lamp Stage 1 15 Switch 0 l 16 Fanwheel 17 Electric panel 18 Contactor 19 Thermaloverloadprotection 20 Motor 21 Lockingdevice flange 22 Solenoidv...

Page 4: ...Flange burner tube Measure B Burner head Standard 290 260 Burner head Long design 390 360 595 290 155 158 B 610 321 400 405 171 215 78 00 02 BURNER HEAD Brake plate 130 The net calorific value of 11 8...

Page 5: ...171 215 79 00 02 BURNER HEAD Brake plate 120 BURNER HEAD Brake plate 110 10 0 13 0 10 0 13 0 3 5 4 0 2 0 3 0 7 0 9 0 3 5 4 0 2 0 3 0 7 0 9 0...

Page 6: ...TECHNICAL DATA DIMENSIONS OF FLANGE 171 225 37 00 01 14 226 254 295 160...

Page 7: ...is obtained If larger nozzles are usedthepreadjustmentofboththeair volumeandthenozzleassemblymust be increased Awhistlingsoundmaybeheardwhich can be eliminated or reduced as fol lows Increase the noz...

Page 8: ...stage Set the operating switch S2 on low capacity I Loosenthescrew A and turn the damper to the position wan ted Tighten the screw A again Second stage Set the operating switch S2 on high capacity II...

Page 9: ...il supply 171 305 65 01 01 SERVICE OF BURNER HEAD alt A SERVICE OF BURNER HEAD alt B NOTE For maintenance of the brake plate nozzles electrodes etc when using a long design of the burner tube you have...

Page 10: ...itch high low capacity S3 Controlthermostat S4 Temperaturelimiter S5 Micro switch for hinged door S6 Control thermostat high low capacity S7 Main switch S12 External reset button S20 Main switch T1 Ig...

Page 11: ...n thermostat The burner motor starts an ignition spark is formed the prepurge goes on till the prepurge period expires and the solenoid valve 1 opens 2 2 Solenoidvalve1opens Oil mist is formed and ign...

Page 12: ...pingapipesystemusuallycomprises 4elbows anon returnvalve acut off valve and an external oil filter Thesumoftheseindividualresistances is so insignificant that they can be disregarded Thetablesdonotinc...

Page 13: ...h return port R closed MOUNTING DISMOUNTING BY PASS PLUG In a 2 pipe system excess oil is led back direct to the oil tank In a 1 pipe system the by pass plug must be removedsothatthereisafreepassage b...

Page 14: ...255 219 22 43 266 229 23 34 277 238 24 23 287 247 25 07 297 256 25 91 307 264 26 70 317 272 6 00 22 34 265 228 23 42 278 239 24 47 290 250 25 46 302 260 26 43 313 270 27 49 326 280 28 27 335 288 29 13...

Page 15: ...not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue dr...

Page 16: ...B20 B30 B40 B45 02119815004 B50 B60 B70 B80 040588622001 B55 040588622002 B65 Enertech AB declares under sole responsibility that the above mentioned product is in conformity with the following stand...

Page 17: ......

Page 18: ...the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If...