7. Parameter Description

Page 10

7.1 Power:

 Meter can either display 

W

 or 

VA

 or 

VAR

 (total and phase wise) one at a 

                   time. This is site configurable. Refer to programming manual on how to 
                   change load type. 
                   Power will auto scale on the display and “K” or “M” will display accordingly 
                   to represent the power in Kilo or Mega (depending upon load). 

7.2 Energy:

 Meter can either display 

Kwh

 or 

KVAh

 or 

KVARh

 (total and phase wise) 

                    one at a time. This is site configurable. Refer to programming manual on 
                    how to change load type. Below are some sample screens. 

                                
                            
       

Energy will reset to zero in 2 cases;-
    a.) Energy Overflow: Meter caluculate energy till 42 Lakhs, after that it reset to zero.
    b.) Manual Reset;- User can manually reset the energy in the programming mode.
 
In both cases, meter will automatically save the energy to old integrated parameters 
before clearing.

LCD

LCD

LCD

LCD

LCD

Series

Series

Series

Series

Series

ENERSOL

ENERSOL

ENERSOL

ENERSOL

ENERSOL

MFLR09

MFLR09

MFLR09

MFLR09

MFLR09

PROG

PROG

PROG

PROG

PROG

COM

COM

COM

COM

COM

            Watt:         r-1.12K

            VAR:         r-1.12K

            VA:              r1120

            Tot:      3.59KVA

            Tot:      3.12KVAR

LCD

Series

ENERSOL

MFLR09

PROG

COM

            Tot:      1.79KW

                0002504.3KWh

              y1.12K      b1.12K

              y1.12K      b1.12K

              y1112         b1120

                0003904.3KVAh

                0003504.3KVARh

Row 1

: Total Watt. Display

reads as total 1.79 Kilo watt.

Row 2:

 Total KWh. Display

Reads as 2504.3 Kwh or 
2504.3 units of active energy.

Row 1

: Phase wise watt. Display

reads as R phase = -1.12 Kilo watt.
negative value means CT is installed
in reverse direction.

Row 2:

 Display reads as

             Y phase = 1.12 Kilo watt
             B phase = 1.12 Kilo watt

Row 1

: Phase wise VAR. Display

reads as R phase = -1.12 Kilo VAR.

Row 2:

 Display reads as

             Y phase = 1.12 Kilo VAR
             B phase = 1.12 Kilo VAR

Row 1

: Phase wise VA. Display

reads as R phase = 1120 VA

Row 2:

 Display reads as

             Y phase = 1112 VA
             B phase = 1120 VA

Row 1:

 Total VA . Display 

reads as total 3.59KVA.

Row 2:

 Total KVAh. Display

Reads as 3904.3 KVA or 
3904.3 units of apparent energy.

Row 1:

 Total VAR. Display

reads as total 3.12KVAR.

Row 2:

 Total KVARh. Display

Reads as 3504.3 KVArh or 
3904.3 units of Reactive energy.

Summary of Contents for MFLR09

Page 1: ...User Manual MFLR09 Energy Meter...

Page 2: ...r 10 7 2 Energy 10 7 3 Power factor 11 7 4 Ampere 11 7 5 RPM 12 7 6 Energy Reset 12 7 7 Meter Run Hours 13 7 8 Power ON Hours 13 7 9 Power Interruptions 13 7 10 Diagnosis 14 8 Interface and Input term...

Page 3: ...ications User can access the device remotely with ease 1 Bright and easy to read 16x2 LCD display with blue back light and white text 2 All basic electric parameter along with Active reactive apparent...

Page 4: ...e on the meter 1 It is advised to always use skilled technicians to operate install the meter 2 Always use complete personal protection equipments before handing operating installing maintaining any e...

Page 5: ...CT Shorting Block 1 Never Connect CTs of this toroidal meter to the electric earth or any other earth connection 2 Never short S2 of all CTs Use only Enersol recommenced connection diagram while makin...

Page 6: ...ither Active or Reactive or Apparent Energy Power On site con gurable port settings 1 Slave ID from 1 to 247 2 Baud From 1200 to 38400 3 Parity None Even Odd On site con gurable from 0 001 to 9999 Not...

Page 7: ...Current rating Single Phase Con guration MFL09 meter without RS485 port Class 0 5 60Amp Current rating Single Phase Con guration MFLR09 meter with RS485 port Class 1 60Amp Current rating Single Phase...

Page 8: ...otal PF 6 DG RPM Meter calculate DG RPM 7 Energy Meter calculate all 3 energies i e Wh VArH VAh only one available at a particular time 8 Run Hours Meter calculate Run hours i e total time for which a...

Page 9: ...hase PF Total VAR R Phase VAR Y Phase VAR B Phase VAR 3 VA Estimation Only applicable when voltage and current have pure sinusoidal waveform This formula can only be used for approximation This formul...

Page 10: ...SOL ENERSOL ENERSOL MFLR09 MFLR09 MFLR09 MFLR09 MFLR09 PROG PROG PROG PROG PROG COM COM COM COM COM Watt r 1 12K VAR r 1 12K VA r1120 Tot 3 59KVA Tot 3 12KVAR LCD Series ENERSOL MFLR09 PROG COM Tot 1...

Page 11: ...IB 3 In case of single phase Iavg IR LCD LCD LCD Series Series Series ENERSOL ENERSOL ENERSOL MFLR09 MFLR09 MFLR09 PROG PROG PROG COM COM COM Tot 0 855L PF PF r0 855L Amp r5 000 0002504 3KWh LCD Seri...

Page 12: ...value got stored to Old parameters before clearing the energy register LCD LCD LCD LCD LCD Series Series Series Series Series ENERSOL ENERSOL ENERSOL ENERSOL ENERSOL MFLR09 MFLR09 MFLR09 MFLR09 MFLR09...

Page 13: ...ment in the power interruptions before and after auxiliary power interruptions LCD LCD LCD LCD Series Series Series Series ENERSOL ENERSOL ENERSOL ENERSOL MFLR09 MFLR09 MFLR09 MFLR09 PROG PROG PROG PR...

Page 14: ...to 60A Ph N Aux Sup 90 300V 2VA RS485 DANGER Turn o power before working R CT Y CT B CT RS485 V1 V2 V3 Vn R Voltage B Voltage Y Voltage a CT Connections Site engineer can check whether CT is connecte...

Page 15: ...l internally correct the CT if it is connected in wrong direction Total power and Energy will remains una ected Q How meter notify the site engineer about CT direction A Meter re ect CT direction unde...

Page 16: ...ference If network is con gured as Single phase then phase sequence doesn t matter and meter start showing 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Voltage inputs 80 480VAC LL Current Input 50mA t...

Page 17: ...COM Tot 1 79KW 0002504 3KWh Calibration LED Up Button Communication Status LED Programming Button Enter Button Page Button Down Button 6 7 9 8 10 5 4 Page 17 8 Interface Input Terminals 8 1 Meter Fron...

Page 18: ...tricparametercategory AvailableCategories are 1 InstantParameters 2 IntegratedParameters 3 SetParameters 4 OldIntegratedParameter 6 Diagnosis DownButton useforscrollingElectricparameterinBackwarddirec...

Page 19: ...unting Lock Terminal Numbering Terminal Numbering Input R Phase Voltage Input R Phase CT Black Wire Input R Phase CT Red Wire Input Y Phase Voltage Input B Phase Voltage Input RS485 wire Input Neutral...

Page 20: ...Total VARh Phase wise VAR RPM If load type is Active If load type is Active If load type is Apparent If load type is Apparent If load type is Reactive If load type is Reactive Back to page Back to pa...

Page 21: ...r ON Hours Total Power ON Hours Total Power ON Hours Total Power Interruptions Total Power Interruptions Total Power Interruptions If load is Active If load is Apparent If load is Reactive Back to pag...

Page 22: ...Instant Parameters page Back to page old Wh old VAh old VARh old Run Hours old Run Hours old Run Hours old Power ON Hours old Power ON Hours old Power ON Hours old Power Interruptions old Power Interr...

Page 23: ...parity using key among followings EVEN ODD NONE default value id EVEN Press key and then press to move to next page Press key to save the changes press key till meter start blinking YES and then press...

Page 24: ...1 V2 V3 Vn V1 V2 V3 Vn V1 V2 V3 Vn V1 V2 V3 Vn V1 V2 V3 Vn 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Voltage inputs 80 480VAC LL Current Input 50mA to 60A Ph N Aux Sup 90 300V 2VA RS485 DANGER Turn...

Page 25: ...Diameter 10mm 5 Case Type Metal Casing 1 P1 side of the CT Metal Side Keep this towards line side 2 P2 side of the CT epoxy Side Keep this towards load side 3 Black wire is S1 and Red Wire is S2 1 2...

Page 26: ...ranging from 1 to 247 Function Code As Per the MODBUS standard the function code for the Read Holding Register is 03 in Hexadecimal Start Address This is a 32 bit value Send as MSB and LSB The formula...

Page 27: ...EE 754 representation for oat value As per IEEE 754 46BA2800 in hexadecimal is oat representation of 23 8 Kwh Page 27 Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Slave ID Function C...

Page 28: ...r VAR VAR 32 Bit Float 11 3862 R Phase PF PF will be negative for capacitive load and positive for the inductive load 32 Bit Float 12 3864 3866 Reserved 13 3868 R Phase Current Ampere 32 Bit Float 14...

Page 29: ...rgy VAh 32 Bit Float 27 3900 Total Active Energy Wh 32 Bit Float 28 3902 Total Reactive Energy VArh 32 Bit Float 29 3904 3930 Reserved 30 3932 DG RPM 32 Bit Float 31 3934 Total Power ON Hours Seconds...