background image

3

PAQG Models: 

 

WARNING: 

On PAQG and PANG models, you must 

connect an in-line directional valve to be able to release 
system pressure and return oil to the reservoir. DO NOT 
release pressure by disconnecting a pressurized line. 
Handling pressurized hydraulic lines can result in severe 
personal injury caused by sudden release of pressurized 
oil.

See illustration 5. For this model, the tool used must have a 
valve in order to release system pressure to the reservoir. If the 
tool does not have a control valve, you must install a remote 
directional valve.

If the tool has a valve, thread a hose into pressure port 

(A)

 of 

the pump and connect the hose to the pressure port of the tool. 
Connect a return line hose from the valve to the tank port 

(B)

.

If you need to install a valve, connect a hose from the pressure 
port 

(A)

 of the pump to the pressure port of the remote valve. 

Connect return line hose from the valve back to the tank port 

(B)

Connect a hose from the valve to the tool. (Recommended Valves: 
Enerpac VC Series manual, or VS/VE Series electro-actuated 
control valves.)

 NOTE:

  Hose fittings must be torqued. See Torque Specifications 

Table to the left.

PANG Models:

 The manifold is designed for custom-made 

valves. PANG models are shipped with a cover and gasket, which 
are bolted to the manifold block. Remove the four bolts, the cover, 
and the gasket. Bolt a valve on the manifold using the four holes 

(C)

 in the manifold block. The mounting holes have M12 x 1,75 

threads, which are 0.60” [15,2mm] deep. Connect hoses to valve 
outlet ports.

5.4 Venting

The pump reservoir must always be vented prior to use. Use 
either the “vent screw” or “vent/fill assembly”.

a) Vent Screw:

 See illustration 7A, item 1. The vent screw is 

the primary means to vent the reservoir. It is located near the 
hydraulic outlet port on top of the reservoir. To allow venting, 
open the screw 1/2 to 1 full turn. To avoid damaging the threads 
when closing the vent screw, tighten only until the screw head 
slightly compresses the O-ring. Apply only about 8-10 in-lbs. [1 
Nm] of torque.

b) Vent/Fill Assembly:

 See illustration 7B, item 2. The vent/fill 

assembly is located on the air inlet end of the pump, opposite the 
vent screw. This assembly serves 3 functions; vent, fill port, and 
return-to-tank port.

To use as a vent, pull up the vent/fill assembly until the first detent 
is reached (see illustration 8). This is the vented position.

To use as a fill port, pull up the vent/fill assembly past the first 
detent. Then, completely remove the assembly from the reservoir. 
If oil level is low, add oil as described in Section 5.6.

To use as a return-to-tank port, remove the hex plug from the 
vent/fill assembly and install a compatible return line. Torque 
return line fitting at the vent/fill connection to 15-20 ft. lbs. [20-27 
Nm].  

CAUTION:

 Pump reservoir must be vented using one 

of the two vent options. Failure to do so may cause 
cavitation and pump damage.

5.5 Mounting Pump

The pump should be mounted only in the horizontal position.

NOTE:

 Vertical mounting is not recommended and may result in 

hydraulic oil leakage.

a) Without Mounting Brackets: 

The four holes in the bottom of 

the reservoir should be used for bolting through the mounting 
surface into the reservoir. Use the #10 x 5/8” fasteners included 
with pump, or allow no more than 3/4” [19 mm] thread engagement 
into reservoir.

NOTE: 

A mounting bracket kit, MTB1, can be ordered from 

Enerpac.

b) With Mounting Brackets: 

Models with brackets have model 

numbers ending with the letter ‘B’. The mounting bracket may 
be mounted on the pump or shipped separately. To mount the 
bracket on the pump, use the #10 x 5/8” fasteners included with 
pump, or allow no more than 3/4” [19 mm] thread engagement 
into reservoir. Mount the pump to the mounting surface using the 
four slots in the mounting bracket.

5.6 Oil Level

Always check oil level with all cylinders or tools in the fully 
retracted position. If they are advanced when the pump is filled, 
the reservoir will be over-filled when they are retracted. 

Use the sight glass on the end of the pump to check the oil level. 
The reservoir is full when the pump is positioned horizontally, and 
oil level is up to, but not above, the top of the sight glass. If oil 
level is low, remove vent/fill assembly from reservoir (See Section 
5.4b) and add oil as required.

6.0 OPERATION

6.1 Oil Level

Check the oil level of pump and add oil if necessary (See Section 
5.6).

6.2 Venting Pump

Make sure the pump reservoir is vented (See Section 5.4).

6.3 Treadle Operation (PATG Models Only): 

See illustration 9.

a) To Advance Cylinder: 

Depress the “PRESSURE” end of treadle 

and the pump will start to pump hydraulic oil to the system.

b) To Hold The Cylinder Position:

 The pump will stop and hold 

pressure when the treadle is in the free/neutral position (treadle 
is not depressed in either “PRESSURE” or “RELEASE” positions.)

c) To Retract Cylinder:

 Depress the “RELEASE” end of the 

treadle to retract cylinder. To stop the cylinder from retracting, 
release the treadle and return it to the hold position.

Reviews: