12
Installation overview
Note:
Solar heat exchange coil is optional.
ATTENTION:
-
The one-way safety valve must be installed. If not, it could cause damage to the unit, or even
hurt people. The set point of this safety valve is 0.7 MPa. For the installation place please refer
to the pipeline connection sketch.
-
The discharge pipe connected to the one-way safety valve is to be installed in a continuously
downward direction and in a frost-free environment.