16
The included wall control is 40405 (intented for EVO5 500 HRV and EVO5 700 HRV HEPA Venmar units only) or 40410 (intented for
HRV 5.1 and HRV 7.1 HEPA Broan units only). The wall control is in OFF mode when power is applied for the first time.
After a power failure, the wall control returns to its original operation mode.
VC0131
LCD screen.
Backlight: If the backlight is
not illuminated, the first key
pressed (no matter which key)
shall turn on the backlight. The
backlight remains illuminated for
10 seconds after the last key is
pressed.
MODE key
TURBO function key
ON/OFF key.
When wall control is OFF, the
unit is on stand-by mode, so
it will only respond to override
wall control (if present). Only
the house icon appears on LCD
screen. When wall control is
ON, the house icon is still there,
and the label mode in which the
unit operates appears at the
bottom of LCD screen. See
operation modes for more details.
ECO mode key
4.6.1 O
PERATION
M
ODES
4.6
M
AIN
W
ALL
C
ONTROL
U
SE
When the wall control is ON, press the MODE key to choose the operation mode of the ventilation unit.
Operating Mode label will then appear on LCD screen (AUTO, ECO, CONT and RECIRC).
AUTO M
ODE
The ventilation unit exchanges air intermittently on a one-hour cycle as follows: exchanges air during 20 minutes on low speed
and then recirculation on high speed for 40 minutes (or OFF for 40 minutes, see section 4.6.3). Repeat cycle after the 40-minute
period.
NOTE: The outdoor temperature value displayed during AUTO recirculation or AUTO off cycle period comes from the reading
while the unit is performing air exchange (first part of AUTO mode cycle). Also, keep in mind that outdoor temperature
reading is taken from the unit fresh air from outside port; due to the lenght of the insulated duct, the result of the reading is
slightly different from the real outside temperature.
F
IRST
PART
OF
THE
CYCLE
L
AST
PART
OF
THE
CYCLE
40 minutes of
recirculation on
high speed
40 minutes OFF
in AUTO mode
OR
20 minutes of air
exchange in low
speed