17.10
Defrost cycle
The defrost cycle starts when the evaporator temperature is < -7 ºC and
finish when the temperature is >13ºC.
Parameters
Description
Value
D
ON
Start defrost cycle
---
D
OFF
End defrost cycle
---
T
ON
Start defrost temperature
-7 °C
T
OFF
End defrost temperature
13 °C
DT
MAX
Maximum defrost time
8 min
DI
Time between next defrost
45 min
Gc09
Time delay to invert the 4 way valve polarity.
102 s
Gc09
Time delay to frequency decrease
100 s
NOTE:
During the defrost cycle the fans remain OFF