![Energie INVERTER 4/12 Installation And Instruction Manual Download Page 21](http://html1.mh-extra.com/html/energie/inverter-4-12/inverter-4-12_installation-and-instruction-manual_2409983021.webp)
ENERGIE
Page | 19
15.9
Ligação eléctrica
WARNING: The electrical installation must be performed in
accordance with local regulations and by a qualified professional.
Open the front panel, and open the power supply access.
The power supply must go through the wire access and be connected to
the power supply terminals in the controlling box. Then connect the 3-
signal wire plugs of the wire controller and main controller.
To connect the room thermostat and remote control (hot/ cold) the
installer should open the top panel, open the electrical box and do the
electrical connections according to the supplied wiring diagram.
The appliance must be fitted with means for disconnection from the
supply mains having a contact separation in all poles that provide full
disconnection under overvoltage category III conditions, and these
means must be incorporated in the fixed wiring in accordance with the
wiring rules.
An all-pole disconnection switch having a contact separation of at least
3mm in all poles should be connected in fixed wiring.
The wiring must be completed by professional technicians in
accordance with circuit diagram.
Power supply circuit must have earth wire, the earth wire of power
should be connected with external earth wire safely. And the external
earth wire must be in order.
The creepage protection device must be settled in accordance with the
relevant national technical standards for electronic equipment.
The power wire and signal wire should be neatly arranged. High voltage
wire and low voltage wire must be separated and free from any
interference, and they must be free from any pipe and valves of the unit.
When all the wiring is completed, the power can only be connected after
a double check. Power Specifications.
Remove the front panel
Summary of Contents for INVERTER 4/12
Page 13: ...ENERGIE Page 11 1 11 1 D Di im me en ns si io on n Wateroutlet WaterInlet Drainage...
Page 15: ...ENERGIE Page 13 1 13 3 C Co oo ol li in ng g H He ea at ti in ng g c ci ir rc cu ui it t...
Page 56: ...ENERGIE Page 54 21 4 Central heating cooling and DHW 21 5 DHW...
Page 58: ...ENERGIE Page 56...
Page 60: ...ENERGIE Page 58...