Enerdrive MagnaSine ME AGS Operator'S Manual Download Page 1

ME AGS

Auto Gen Start 

Network System with 

Inverter and Remote 

for Coach Generators

Operator’s Manual

Summary of Contents for MagnaSine ME AGS

Page 1: ...ME AGS Auto Gen Start Network System with Inverter and Remote for Coach Generators Operator s Manual...

Page 2: ...2 2010 Enerdrive Pty Ltd...

Page 3: ...ystem with Inverter and Remote for Coach Generators Table of Contents SAVE THESE INSTRUCTIONS This manual contains important safety instructions Section 1 Overview 2 Configuration 3 Installation 4 Ope...

Page 4: ...n the inside temperature of the coach or a low battery condition These features allow you to leave pets and precious items in your coach while you enjoy a day away golfing touring or just sight seeing...

Page 5: ...Diesel generators the controller is configured with the Diesel Petrol jumper positioned over the two left hand pins as shown below factory default For most petrol as well as other diesel generators yo...

Page 6: ...ith version 0 5 or higher version 0 5 or higher REMOTE Stand alone switch Stand alone switch PORT pigtail direct to a c thermostat pigtail direct to a c thermostat or sensor only or sensor only START...

Page 7: ...leshooting Wiring is much easier if the controller is mounted within easy access to the generator s remote wiring Pre drill the four 1 8 holes if necessary 2 Remove the 8 pin connector from the contro...

Page 8: ...best results NOTE The thermistor that is used to sense the coach s interior temperature is located on the back of the AGS Switch It is vital that the switch be placed where interior room temperatures...

Page 9: ...re interior room temperatures can be accurately monitored by the thermistor Keep the switch away from heating and air conditioning ducts window drafts and avoid mounting it on the coach s exterior wal...

Page 10: ...10 2010 Enerdrive Pty Ltd 3 Installation Figure 3 AGS Wiring Diagram...

Page 11: ...2010 Enerdrive Pty Ltd 11 3 Installation Figure 4 AGS Connector Pin Legend from left to right...

Page 12: ...tage setting is reached NOTE To change this setting slowly rotate the knob marked START VOLTS clockwise to increase the voltage or counterclockwise to decrease voltage The range is 10 VDC to 12 VDC NO...

Page 13: ...evening and early morning It is adjustable for five pre selected time ranges To set quiet time turn the dial either counter clockwise or clockwise to the hours required 9 7 9 PM to 7 AM 9 8 9 PM to 8...

Page 14: ...temperature or low battery voltage conditions Temperature and voltage settings are selected using the AGS Controller page 11 AutoGenSt Test Starts and runs the generator for 30 seconds fully testing t...

Page 15: ...22 VDC 3 Activate the system by setting the AGS to AutoGenSt Enabl This is the normal operating setting When the coach s inside temperature reaches the START TEMP F or the START VOLTS DC setting the L...

Page 16: ...VDC or 20 VDC to 24 VDC Quiet Time Range 9PM to 7AM 9PM to 8AM 9PM to 9AM 10PM to 8AM 11PM to 8AM Clock 24 hour Generator Run Range 1 to 5 hours 2 hours factory setting Connections Screw Terminals rea...

Page 17: ...LUTION RED GEN FAULT Gen won t start Check Gen start wiring Turn off then enable to reset RED GEN FAULT Gen won t stay on Check Gen B wiring check gen turn off then enable to reset GREEN BLINK GEN STA...

Page 18: ...ative parts Enerdrive s limit of liability under the limited warranty shall be the actual cash value of the product at the time the original purchaser returns the product for repair determined by the...

Page 19: ...Templates Remote Control...

Page 20: ...20 Part Number 64 0005 Rev 6 04 MagnaSine by Enerdrive Unit 10 1029 Manly Road Tingalpa Queensland Australia 4173 Ph 1300 851 535 email sales enerdrive com au www enerdrive com au...