Enerdrive ePRO Plus Battery Monitor Owners Manual (Rev. 1.03)
Page 24
Table 10
Alarm
type
On value
(default)
O value
(default)
Range
Alarm description
OFF
-
-
-
Alarm not used
V.LOW
(bank1)
10.5V
11.0V
7.0V -
70.0V
Low battery voltage. When the voltage
falls below the On value, the associated
alarm will be activated. When the voltage
rises above the O value, this alarms will
be deactivated again.
V.HIGH
(bank1)
16.0V
15.5V
High battery voltage. When the voltage
rises above the On value, the associated
alarm will be activated. When the voltage
falls below the O value, this alarm will
be deactivated again.
SOC.LOW
(bank1)
40%
80%
0% - 99%
Low State of Charge. When the SoC falls
below the On value, the associated alarm
will be activated. When the SoC rises
above the O value, this alarm will be
deactivated again.
TIME.LOW
(bank1)
0h30m
1h00m
1min -
24hrs
Low time remaining. When the time
remaining falls below the On value, the
associated alarm will be activated. When
the time remaining rises above the O
value, this alarm will be deactivated
again.
I.CHARGE
(bank1)
10.0A
9.0A
1.0A -
600.0A
High charge current. When the charge
current exceeds the On value, the
associated alarm will be activated. When
the charge current falls below the O
value, this alarm will be deactivated
again.
I.DISCH
(bank1)
10.0A
9.0A
High discharge current. When the
discharge current exceeds the On value,
the associated alarm will be activated.
When the charge current falls below the
O value, this alarm will be deactivated
again.