Page 17
Enerdrive ePRO Inverter / Charger Owners Manual
Factory setting = OFF
ASB mode
ON =
ASB mode on
OFF =
ASB mode o
ff
Factory setting 5 = OFF
Factory setting 6 = ON
Battery type / Charge program
1
)
5 = OFF
Battery type = Flooded
6 = OFF
Absorption voltage = 14.4V or 28.8V
Float voltage = 13.5V or 27.0V
5 = ON
Battery type = GEL
6 = OFF
Absorption voltage = 14.2V or 28.4V Float
voltage = 13.5V or 27.0V
5 = OFF
Battery type = AGM
6 = ON
Absorption voltage = 14.3V or 28.6V Float
voltage = 13.3V or 26.6V
5 = ON
Battery type = Custom (created by Dashboard)
6 = ON
Absorption voltage = set by Dashboard Float
voltage = set by Dashboard
Factory setting = OFF
AC Input Power Boost
ON =
AC Input Power Boost on
OFF =
AC Input Power Boost o
ff