Enerdrive ePRO Inverter / Charger Owners Manual
Page 16
3.3 DIP Switch Settings Overview
During step 3 of the installation guide, you can alter the factory settings
of the DIP switches to change the functionality of the ePRO Combi on
a few points. For additional information about the settings, see the
previous chapter (3.2). The following settings can be made :
Setting Description
Factory setting = OFF
Local / External Programming
ON (External) =
DIP switches 2 to 7 or 9 are
ignored and the ePRO Combi will always load the
parameter settings as con
fi
gured in Dashboard.
OFF (Local) =
The local DIP switch settings are used. All
other parameters are set to the factory default settings.
Factory setting = OFF
Inverter output frequency
ON =
Output frequency is 60Hz
OFF =
Output frequency is 50Hz
Factory setting = ON
Low battery protect
ON =
Low battery protect is on
OFF =
Low battery protect is o
ff
(immediate inverter
shutdown when the battery voltage is < 8.0V)