Enerdrive DOMETIC EN43510 Owner'S Manual Download Page 25

Battery

over Discharged

Battery level shows

empty, battery frame

and fault icon blink

When the battery voltage is restored to 

or above the LVR (low voltage 

reconnect voltage), the load will 

recover.

The controller will automatically turn 

the system off. When the temperature 

declines to below 55 ºC, the 

controller will resume. 

When the heatsync of controller exceeds 

85

˚C

, the controller will automatically 

cut off input and output circuit. When 

the temperature below 75

˚C

, the 

controller will resume operation.  

 Check whether the battery voltage 

matches with the controller working 

voltage.

 Please change to a suitable 

battery or reset the working voltage. 

① 

Please reduce the number of loads 

connected to the load circuits of the 

controller.  

 Restart the controller.

 Check carefully loads connection,

clear the fault.

 Restart the controller.

 Carefully check load connections

before continuing operation.

Battery

Overheating

Controller 

Overheating

System

Voltage Error

Load Overload

Load Short

Circuit

Battery frame and

fault icon blink

PV/BATT indicator fast flashing 

-See Figure 4.2  reduce 

charging mode

Reduce load connected to the controller

Load and fault icon 

blink 

www.enerdrive.com.au

Page 25

Summary of Contents for DOMETIC EN43510

Page 1: ...Owner s Manual Rev 1 3 2022 EN43510 MPPT Solar Controller 12 24V 10Amp EN43520 MPPT Solar Controller 12 24V 20Amp EN43530 MPPT Solar Controller 12 24V 30Amp EN43540 MPPT Solar Controller 12 24V 40Amp...

Page 2: ...Misuse may result in damage to the unit and or cause harm or serious injury Read manual in its entirety before using the unit and save manual for future reference MPPT Solar Controller Owners Manual R...

Page 3: ...ndirect consequential or incidental which might arise out of the use of such information The use of any such information will be entirely at the user s risk 3 Reminds you that if this manual is in any...

Page 4: ...NFORMATION 3 DISPLAY 4 PARAMETERS SETTING 5 OTHERS 6 TECHNICAL SPECIFICATIONS 3 1 OVERVIEW 4 1 BATTERY PARAMETERS 4 1 1 SUPPORTED BATTERY TYPES 4 2 LOAD WORKING MODES 5 1 PROTECTION 5 2 TROUBLESHOOTIN...

Page 5: ...reverse polarity This controller is suitable for RV Marine Remote Off Grid monitoring and many other applications CE certification LVD EN IEC62109 EMC EN61000 6 1 3 LCD display Advanced MPPT technolog...

Page 6: ...roductCharacteristics RTS Port If the temperature sensor is short circuited or damaged the controller will charge discharge according to the voltage set point at the default temperature setting of 25...

Page 7: ...is highly recommended if mounted in an enclosure Never install the controller in a sealed enclosure with flooded batteries Battery fumes from vented batteries will corrode and destroy the controller c...

Page 8: ...arvest from the PV array MPPT controller overdrive Note The recommended maximum solar wattage input for the EN43540 controller is 600 watts 12V You can however overdrive the MPPT controller Please not...

Page 9: ...array due to the influence of environmental temperature which may make the probability of damage to the controller rise Therefore it is very important to configure the system correctly Excess Solar a...

Page 10: ...30A 40A EN43520 EN43530 EN43540 BATTERY AND LOAD WIRE SIZE The battery and load wire size must conform to the rated current the reference sizes as below are a guide only MODEL RATED CHARGE CURRENT RAT...

Page 11: ...hen wiring INSTALLATION PROCEDURE Step 1 Determination of Installation Location and Heat dissipation Space Determination of installation location The controller shall be installed in a place with suff...

Page 12: ...of 1 battery 2 load 3 PV array in accordance with Figure 1 Page 6 Schematic Wiring Diagram and disconnect the system in the reverse order 3 2 1 CAUTION While wiring the controller do not close the cir...

Page 13: ...nected to the controller the default setting for battery charging or discharging temperature is 25 C without temperature compensation Closing the battery fuse circuit breaker will switch on the contro...

Page 14: ...problem 3 DISPLAY 3 1 OVERVIEW INDICATOR COLOUR STATUS INSTRUCTION When load manual mode is selected you can turn the load On Off via the button ENTER Press the button Press the button MODE NOTE Pres...

Page 15: ...Voltage Current Generated Energy Estimated Battery Capacity In Charging Battery Voltage Current Temperature Battery Type Load ON Load OFF Current Consumed Energy Load mode PV Array Battery Load INDIC...

Page 16: ...erfaces 3 2 OPERATION 1 Browse Interface 2 Load Parameter Display Clear the recorded energy Press the button and hold for 5s under the PV recorded energy interface and the value will then be flashing...

Page 17: ...type interface is flashing to cycle through the battery types Step 2 Press the button to confirm the battery type 2 Battery Type 3 Press the button and and hold 5s under the battery temperature interf...

Page 18: ...Flooded LiFePO4 4S 8S Li NiCoMn O2 3S 6S 7S Lithium Battery User 2 3 When the default battery type is selected the battery voltage parameters cannot be modified To change these parameters select the U...

Page 19: ...s the 3 Press the button to modify the voltage 12 24V button again to display the current SYS value 4 Press the button to confirm and enter the next parameter 6 Press the increase by 0 1V long press t...

Page 20: ...12 6V 12 8V 9 17V 16 0V 15 0V 15 0V 15 0V 15 0V 14 6V 14 4V 14 2V 14 6V 14 8V 15 0V 15 0V 16 0V 16 0V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 9 17V 14 8V 14 6V 14 6V 14 5V 14 5V 29...

Page 21: ...r 3 13 hours after sunset Load will be on for 14 hours after sunset Load will be on for 15 hours after sunset Test mode Manual mode default load ON 2n 201 202 203 213 Disabled Disabled Disabled Load w...

Page 22: ...age it will automatically stop battery charging to prevent battery damage caused by over charging Always ensure polarity of battery connections prior to connection Incorrect polarity will cause damage...

Page 23: ...seconds If the short circuit is still present the controller will repeat this process a further 4 times After the 5th attempt to reconnect the controller will stay disconnected until the load is manu...

Page 24: ...he OVD over voltage disconnect voltage and disconnect the PV When the internal temperature of the controller is higher than 85 C the controller will experience a 5 drop off in performance for every de...

Page 25: ...e operation Check whether the battery voltage matches with the controller working voltage Please change to a suitable battery or reset the working voltage Please reduce the number of loads connected t...

Page 26: ...ion present and clean accordingly Check the unit is functioning correctly with the correct LED indicators Keep any eye out for any error codes requiring further trouble shooting Confirm that all the s...

Page 27: ...3 8 32V BatteryVoltage 2V 72V 10A 20A 30A 40A 10A 150W 12V 300W 24V 180W 12V 360W 24V 98 20 175x143x48 120x134 12AWG 4mm 12AWG 4mm 6AWG 16mm 10AWG 6mm 8AWG 10mm 6AWG 13 2mm 6AWG 16mm 6AWG 16mm 160x149...

Page 28: ...NOTES Page 28 MPPT Solar Controller Owners Manual Rev 1 3...

Page 29: ...NOTES www enerdrive com au Page 29...

Page 30: ...Dometic Power Control Enerdrive Pty Ltd P O Box 9159 Wynnum Plaza Queensland Australia 4178 Ph 1300 851 535 Fax 07 3390 6911 Email support enerdrive com au Web www enerdrive com au...

Reviews: