16
Figure 13. Installation of Grease alarm
5.2.6. Disposal Pump
Package:
1 pc Heavy-duty disposal pump with Vortex impeller, motor 2,2kW 400V 50Hz
1 pc Gate valve DN65
1 pc Suction pipe DN65, PE
1 pc Rubber coupling
ø75 mm with 2 clamps
1 pc Double flanged pipe DN65, cast iron
1 pc Pipe adapter DN50/65
Installation process
•
The disposal pump unit (pump with motor, double flanged pipe, adapter) is supplied
completely assembled.
•
Drill an opening of
Ø 65 mm using a drill crown in the nozzle at the bottom of the tank.
•
Place the disposal pump on a rubber anti-vibration matt.
•
Attach the suction pipe by the rubber coupling to the tank, and tighten the metal clamps.
•
Connect the suction pipe and gate valve to the double flanged pipe.
Summary of Contents for Greasly-2A
Page 18: ...18 Figure 15 Wiring diagram...