5. INSTALLATION
5.1. Selection of location
Figure 8. Example of installation
Grease separators shall be installed close to the source of wastewater. Do not site the systems
in unventilated rooms, on roads, car parks or in storage areas. The separators shall be easily
accessible to cleaning vehicles.
Before installation of grease separator following conditions shall be checked:
-
The room shall be protected from frost (recommended temperature >15 °C).
-
The room shall be well vented/ventilated.
-
The floor shall be a horizontal, rigid surface capable of bearing an appropriate load.
-
The floor shall be equipped with an integrated drain.
-
To prevent bad odour, separators shall not be sited close to residential buildings, close
to windows and air intakes.
-
The installation location of the separator shall have sufficient light.
-
Separator shall be easily accessible to vacuum vehicles.
-
Space shall be sufficient for the maintenance. Room height shall be 60 cm higher than
grease separator to enable the opening of the covers during the maintenance. Free space of
1 m in front of separator shall be available.
-
Cold and hot water connections available.
-
Inlet pipe with stilling section of min. 1 m available.
-
The inlet and outlet pipelines shall have a gradient of 2%.
-
If the inlet pipe is longer than 10 m it shall be equipped with a separate vent.