Using
special fittings / accessories
RCD
fault current safety equipment / FI protection switch
Status at: August 2017
ESE 406 - 606 (D)HG-GT (ES) Duplex
55
Figure 5-1: FI protection switch
1.
The generator must have been started (see 4.4).
2.
Put the protection switch
(seeFigure 5-1-(1))
into Position 1.
3.
Activate the test switch
(seeFigure 5-1-(2))
.
The switch position displays the result
(seeFigure 5-1-(1))
:
Symbol
Significance
Position I
Protection switch does not trigger.
Fi protection switch is defective.
Position 0
Protection switch triggers.
FI protection switch is working properly.
Table 5.1: FI protection switch test
The device has been tested in compliance with DIN VDE
0100-551.
4.
Bring protection switch
(Figure 5-1-(1))
back into Position 1
in order to be able to operate consumers on the generator
again.
Checking the FI protection
switch:
1
2