Technical
specifications
Checking
the electrical safety
Status at: April 2016
53
Name
Value
Unit
Type
ESE 1008 LG ES DIESEL
DUPLEX SILENT
ESE 1408 DLG ES DIE-
SEL DUPLEX SILENT
Nominal power [PRP] [kVA / kW]
10,0/9,0
14,0/11,2
kVA / kW
Nominal power factor V3~
-
0.8
[cos
φ
]
Nominal power factor V1~
0.9
0.9
[cos
φ
]
Nominal frequency
50
50
[Hz]
Nominal speed
3000
3000
[min
-1
]
Nominal voltage 3~
-
400
[V]
Nominal voltage 1~
230
230
[V]
Rated current 3~
-
20
[A]
Rated current 1~
43.5
30
[A]
Weight
320
320
[kg]
Tank capacity (diesel fuel)
35
35
[l]
Length
1110
1110
[mm]
Width
700
700
[mm]
Height
870
870
[mm]
Sound power level LWA*
96
96
[db (A)]
Sound power level LPA at 7 m
71
71
[db (A)]
Sound power level at work loca-
tion LpA **
88
88
[db (A)]
Protection Class
IP54
IP54
Table 9.1: Generator technical data
Name
Value
Unit
Setting up height above sea level
< 100
[m]
Temperature
< 25
[°C]
Relative air humidity
< 30
[%]
Table 9.2: Ambient conditions for the generator
Power reduction
for each addi-
tional
Unit
1 %
100
[m]
4 %
10
[°C]
Table 9.3: Generator power reduction dependent on ambient conditions
Line
max. line length
Unit
HO 7 RN-F (NSH öu) 1.5 mm
2
60
[m]
Technical specifications
Ambient conditions
Reduced power
Distribution network