Commissioning
RMA42
20
Hauser
6.4
Configuring the device
Configuration steps:
1.
Select the application conditions (only for 2-channel devices) (
2.
Configure the universal input(s) (
3.
Configure the calculations (
4.
Configure the analog output(s) (
5.
Configure relays (if option selected); assign and monitor limit values (
6.
Advanced device configuration (access protection/operating code; saving the current setup/
user setup) (
7.
Configure the display functions (
The following section provides a detailed account of how to set up the two-channel device and the
differential pressure application package (brief overview of the configuration
22, only
available in the two-channel version). If you want to configure a single-channel device, please
proceed as explained in Section 6.4.2.
6.4.1
Step 1: Selecting the application conditions/number of active
input channels
Application conditions of a two-channel device
Call up the Setup menu after performing the post-installation check.
Press ‘
E
’
É
press ‘
+
’
É
‘
Setup
’ is displayed, press
É
‘
E
’.
Select your application conditions in the first point of the setup. The following options are available:
1.
Differential pressure (‘
Diff pressure
’): application package; parameters are automatically
preconfigured for you.
2.
Single channel (‘
1-channel
’): universal input 2 (‘
Analog in 2
’) is deactivated (‘
off
’) from the
software side. The second channel can always be activated at a later stage via
‘
Setup
’
É
‘Analog in 2’
(
3.
Two channels (‘
2-channel
’): universal input 1 (‘
Analog in 1
’) and universal input 2 (‘
Analog
in 2
’) are preconfigured with the following values:
– Signal type (‘
Signal type
’): ‘
Current
’
– Signal range (‘
Signal range
’): ‘
4-20mA
’
The following section provides a detailed description of the "Differential pressure" application
package.
To set up the device in single-channel/two-channel applications, please proceed with the device
setup as explained in Section 6.4.2 (analog input 1 (‘
Analog in 1
’)).
!
Note!
If the application or the parameter selected are subsequently changed, parameters already
configured are retained (e.g. if the differential pressure application is changed to two-channel
É
‘
Calc value 1
’ remains at the Difference parameter).