RMA42
Commissioning
Hauser
29
6.4.6
Step 6: Advanced device configuration (access protection/
operating code, saving the current setup)
Access protection
The access protection locks all the editable parameters, i.e. setup can only be accessed once the 4-
digit user code has been entered.
Access protection is not activated at the factory. However, the configuration of the device can be
protected by a four-digit code.
Activating access protection:
1.
Call up the menu ‘
Setup
’
É
‘
System
’
É
‘
Access code
’
2.
To enter the code with the ‘
+
’ and ‘
-
’ keys, select the desired character and confirm with ‘
E
’.
The cursor goes to the next position. Once the fourth position has been confirmed, the entry
is accepted and the user exits the
‘Access code
’ submenu.
Once access protection has been successfully activated, the lock symbol is shown on the display.
!
Note!
If access protection is enabled, the device locks automatically after 600 seconds if it has not been
operated in this time. The display switches back to the operating display.
To delete the code completely, use the ‘
+
’ and ‘
-
’ keys to select the "
c
" character and confirm with
‘E’.
Saving the current setup/user setup
The current configuration of the device can be saved and is thus available as a specific setup for a
device reset or for a device restart. If you ordered the device with customized settings which you
specified, the preconfigured setup is also saved in the user setup.
Saving the setup:
Call up the menu ‘
Expert
’
É
‘
System
’
É
‘
Save User Setup
’. Confirm by configuring ‘Yes’. See
also
6.4.7
Step 7: Configuring the display functions
The display is split into a 7-segment display section and a color section. The dot matrix section can
be configured separately for each channel.
All the active channels (analog inputs and calculated values) are offered for selection.
To configure the display: press ‘
E
’ and select ‘
Display
’.
Select
É
channel / calculated value and configure one of the following parameters.
É
Contrast
: select contrast (can be configured in stages 1 to 7)
É
Brightness
: select brightness (can be configured in stages 1 to 7)
É
Alternating time
: select the time between automatic switchover between the channels and
calculated values (in seconds: 3, 5, or 10)
‘
x Back
’ takes you back to the higher-order menu.
Off
:
Channel is not displayed.
Activate the display by configuring the color section:
Value/measured value of the channel is displayed on the 7-segment display.
Unit
:
The unit of the channel is displayed
Bar graph
:
The value of the channel is displayed as a bar graph over the entire width.
Bargr+unit
:
Division of the color section, displays value of the channel as a bar graph and unit of the channel
TAG+unit
:
Division of the color section, displays channel name and unit of the channel