RIA46
Wiring
Hauser
37
Connection of the relays (optional)
Relay 1
R12 R11R13
A0010412
Relay 2
R22 R21R23
A0010413
Connection of the analog output
Analog output 1
O15
O16
A0010742
Analog output 2 (optional)
O25
O26
A0010743
Connection of the digital output
Digital output/open collector
OC
D11
D12
A0010744
Connection of the power supply
24 to 230 V AC/DC (-20 % / +10 %) 50/60
Hz
L|+ N|-
A0010746
No grounding conductor is connected for the plastic housing.
For the aluminum housing (optional), a grounding conductor can
be connected at the grounding connection inside the housing.
Interfaces
Interface for configuring with the FieldCare PC software
A0010417