RIA15
Commissioning
Hauser
19
6.1
Operating functions
The operating functions of the process display unit are divided into the following menus. The
individual parameters and settings are described in the "Commissioning" section.
Setup
(SETUP)
Diagnostics
(DIAG)
Device information, display of error messages (
Expert
(EXPRT)
Expert settings for the device setup (
The Expert menu is protected by an access code (default 0000).
7
Commissioning
7.1
Post-installation check and switching on the device
Perform the final checks before commissioning the device.
• Checklist for "post-installation check" (
• Checklist for "post-connection check" (
The device starts after being connected to the 4 to 20 mA circuit. Different device information
appears on the display during the start-up phase.
If you are commissioning the device for the first time, program the setup as described in the
Operating Instructions.
If you are commissioning a device that is already configured or preset, the device starts
measuring immediately as defined in the settings.
Remove the protective film from the display as this would otherwise affect the
readability of the display.
7.2
Operating matrix
Setup menu (SETUP)
Parameter
Values
Description
DECIM
0 DEC
1 DEC
2 DEC
3 DEC
4 DEC
Number of decimal places for display
SC__4
Numerical value
–19
999 to 99
999
Default:
0.0
5-digit value (number of decimal places as configured under
DECIM) for scaling the measured value at 4 mA
Example: SC__4 = 0.0
Þ
0.0 displayed at 4 mA measuring
current
The unit selected under UNIT is used to display the value.