Device configuration
RIA16
20
Hauser
7.4.2
Program information
!
Note!
Press the + or - key to scroll horizontally through the 7 or 8-digit display values.
7.4.3
Alarm limits (NAMUR)
PARAM
É
NAMUR
The alarm limits are set to NAMUR values at the factory.
These values can
– be used as default values (DEF) or
– be edited freely (EDIT)
The following operating positions can be altered if operating item 'Edit' was selected.
The Namur limits are indicated in ascending order.
7.4.4
Test (TEST)
PARAM
É
TEST
É
Options OFF, OUT, DISP
Certain device functions can be tested automatically.
OFF (default)
Open collector: OUT
Display: DISP
Name
Description
Program name 'PNAME'
Displays the name of the software loaded in the device (7-digit)
!
Note!
Display cannot be edited
Firmware version 'FWVER'
Displays the version of the firmware loaded in the device (8-digit)
!
Note!
Display cannot be edited
Name
Description
NAMUR 3.6
Value range : 0 mA to < Namur 3.8
Default: 3.60
NAMUR 3.8
Value range : Namur 3.6 < x < Namur 20.5
Default: 3.80
NAMUR 20.5
Value range : Namur 3.8 < x < Namur 21.0
Default: 20.50
NAMUR 21.0
Value range : Namur 20.5 < x < 25 mA
Default: 21.00