Proline t-mass 65 PROFIBUS DP/PA
Trouble-shooting
Hauser
93
10.2
System error messages
Serious system errors are
always
recognized by the flowmeter as "Fault message", and are
shown as a lightning flash (
$
) on the display! Fault messages immediately affect the
operation. Simulations and positive zero return, on the other hand, are classed and displayed
as "Notice messages".
"
Caution!
In the event of a serious fault, a flowmeter might have to be returned to the manufacturer
for repair. Important procedures must be carried out before you return a flowmeter to
Hauser.
109. Always enclose a duly completed "Declaration of contamination"
form. You will find a preprinted blank of this form at the back of this manual.
!
Note!
Also observe the information on the following pages
10.2.1
Displaying the device status on PROFIBUS DP
Display in the operating program (acyclic data transmission)
The device status can be queried using an operating program (e.g. FieldCare):
Function block SUPERVISION
ACTUAL SYSTEM CONDITION
Faulty connection to PROFIBUS master
(continued)
Network structure
Check permissible fieldbus length and number of spurs.
Fieldbus address
Check fieldbus address: make sure there are no double assignments.
Bus termination
Has the PROFIBUS network been terminated correctly?
Each bus segment must always be terminated with a bus terminator at both ends
(start and finish). Otherwise there may be interference in communication.
t
System or process error messages
System or process errors which occur during commissioning or operation can be displayed in ACTUAL SYSTEM
CONDITION function via local display or by using an operating program
t
Other error (without error message)
Some other error has
occurred
Diagnosis and rectification