Trouble-shooting
Proline t-mass 65 PROFIBUS DP/PA
100
Hauser
10.3
Process error messages
!
Note!
Also observe the information on the following pages:
41 and
10.3.1
List of process error messages
10.4
Process errors without messages
No.
Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic mes-
sage in the PRO-
FIBUS
master
Cause/
Rectification
Q
ual
ity
co
de (HEX
)
M
ea
sured v
aria
b
le status
Qu
ality
sta
tus
Qu
al
ity
substa
tu
s
Li
mits
P = Process error
$
= Fault message (with an effect on the current operation)
! = Notice message (without any effect on the current operation)
422
P: FLOW LIMIT
$
: # 422
0x13
BAD
Sensor fail-
ure
Constant
Meas. flow
exceeded max
limit
Cause:
The measured flow has exceeded the maximum
limit.
Remedy:
Reduce the flow rate or replace the instrument
with a suitable size for the application.
!
Note!
Error can be configured as a fault or notice mes-
sage.
731
P: 0 ZERO-ADJ. N. OK.
$
: # 731
0x13
BAD
Sensor fail-
ure
Constant
Zero adjust is not
ok
Cause:
The saved zero point is inaccurate possibly due
to unstable process or flow conditions.
Remedy:
Stabilize process conditions or relocate the
instrument to a more stable measuring loca-
tion.
Symptoms
Rectification
!
Note!
You may have to change or correct certain settings of the function matrix in order to rectify faults. The functions outlined below, such as DISPLAY
DAMPING, for example, are described in detail in the "Description of Device Functions" manual.
Displayed measured value fluctuates
even though flow is steady.
1. Increase value of the TIME CONSTANT setting
CURRENT OUTPUT function group.
2. Increase value of the DISPLAY DAMPING setting
USER INTERFACE function group.
3. The inlet and outlet lengths must be observed. See installation conditions
4. Consider the use of a flow conditioner. See installation conditions
5. Relocate the meter to a point where there is less flow disturbance
Device displays flow with no actual
flow present.
1. The low flow cut off value is programmed too low. Increase value of the ON VALUE LOW FLOW CUT OFF
setting
PROCESS PARAMETERS function group (Factory setting = 1% of 20mA value).
2. Check for leaks in the pipe line downsteam of the sensor.
3. Reduce or eliminate pressure pulsations in the line.