Electrical connection
Proline Prowirl R 200
38
Hauser
The address must always be configured for a PROFIBUS DP/PA device. The valid
address range is between 1 and 126. In a PROFIBUS DP/PA network, each address can
only be assigned once. If an address is not configured correctly, the device is not
recognized by the master. All measuring devices are delivered from the factory with the
device address 126 and with the software addressing method.
2
98
3
4
5
6
7
8
1
DIP
ON
A0015686
9
Address switch in the connection compartment
Hardware addressing
1. Set switch 8 to the "OFF" position.
2. Using switches 1 to 7, set the address as indicated in the table below.
The change of address takes effect after 10 seconds. The device is restarted.
Switch
1
2
3
4
5
6
7
Value in "ON" position
1
2
4
8
16
32
64
Value in "OFF" position
0
0
0
0
0
0
0
2
98
3
4
5
6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
10
Example of hardware addressing; switch 8 is set to the "OFF" position; switches 1 to 7
define the address.
Software addressing
1. Set switch 8 to "ON".