Proline Prosonic Flow 92F

4

Hauser

General warnings

• Any national regulations pertaining to the installation of devices in hazardous areas must be observed.

• Mounting, electrical installation, commissioning and maintenance of the devices may only be performed by 

technical staff trained in the area of explosion protection.

• Compliance with all of the technical data of the device (see nameplate) is mandatory.

Special conditions

• The device must be integrated into the potential equalization system. Potential must be equalized along the 

intrinsically safe sensor circuits. Further information can be found in the "Potential equalization" chapter on 
Page 7.

Installation instructions

• The cable entries and openings not used must be sealed tight with suitable components.

• The measuring device must only be used in the permitted temperature class. 

The values of the individual temperature classes can be found in the temperature tables on Page 6.

• The manufacturer's specifications for all devices connected to the intrinsically safe sensor circuit must be 

taken into consideration.

• To rotate the transmitter housing, please follow the same procedure as for non-Ex versions. The transmitter 

housing may also be rotated during operation.

• The continuous service temperature of the cable must correspond at least to the temperature range of 

–40 °F and up to +18 °F above the ambient temperature present (–40 °F to (T

a

 +18 °F)).

• All equipment of the measuring system must be included in potential matching (see Page 7).

• The devices may only be used for fluids against which the wetted materials are sufficiently resistant.

• The service connector may not be connected in a potentially explosive atmosphere.

• Install per National Electrical Code. Install intrinsically safe circuits per NEC ANSI/NFPA 70 and 

ISA RP 12.6 respecting the explosionproof integrity of the enclosure.

Approvals

General

The system meets the basic safety and health requirements for the design and construction of devices and 
protection systems designated for use in hazardous areas in accordance with the National Electrical Code. 

Certification number

I.D. 3026261

Inspection authority

FM: Factory Mutual Research

Identification

The system identification must contain the following information:

"

Caution!

The installation instructions for the safe use and application of the system must be observed 

Page 4.

Description of the 
measuring system

The measuring system consists of a transmitter and a sensor. Two versions are available:
• Compact version:

The transmitter and sensor form a mechanical unit.

• Remote version:

The transmitter and sensor are mounted separate from one another and interconnected by means of a 
connecting cable (see also "Electrical connections" (Page 7) and "Cable specifications for connecting cable" 
(Page 7).

Compact version and remote version (transmitter and sensor)

Prosonic Flow 92F**-*****P*****A
Prosonic Flow 92F**-*****P*****W

Cl. I, Groups ABCD
Cl. II, Groups EFG
Cl. III
Cl. I, Zone 1, AEx/Ex d [ia] IIC T6 - T1

Prosonic Flow 92F**-*****P*****H
Prosonic Flow 92F**-*****P*****K

Cl. I, Groups ABCD
Cl. II, Groups EFG
Cl. III
Cl. I, Zone 1, AEx/Ex d [ia] IIC T4 - T1

Summary of Contents for Proline Prosonic Flow 92F

Page 1: ...92F HART PROFIBUS PA FOUNDATION Fieldbus XP Ex d version Division 1 2 Safety instructions for electrical apparatus for explosion hazardous areas according to FACTORY MUTUAL standards Page 3 1 Safety...

Page 2: ...III Group Gases vapours and dust examples Gas Dust Fibre CSC NEC Min ignition temperature J m A B C D E F G 0 02 0 02 0 06 0 18 Acetylene c Class I Class I Class I Class I Metallic powder Class II Cl...

Page 3: ...PA BA128D Proline Prosonic Flow 92F FOUNDATION Fieldbus Table of Contents FM General warnings 4 Special conditions 4 Installation instructions 4 Approvals 4 Description of the measuring system 4 Devi...

Page 4: ...asuring system must be included in potential matching see Page 7 The devices may only be used for fluids against which the wetted materials are sufficiently resistant The service connector may not be...

Page 5: ...SEALED Provides intrinsically safe sensor circuits See control drawings 1 5W 4153 Reinach Switzerland 2006 1 2 3 4 6 5 A 7 5P CAL TM 40 C 40 F 150 C 302 F CF3M 1 4404 F316L Materials DN100 4 DIN EN PN...

Page 6: ...to 383 40 to 392 40 to 392 40 to 140 40 to 266 40 to 383 40 to 392 40 to 392 Prosonic 92F P H K 40 to 140 40 to 266 40 to 383 40 to 392 40 to 392 Ta Tmed F T6 185 F T5 212 F T4 275 F T3 392 F T2 572...

Page 7: ...ess Hauser max 98 ft 30 m complies with these values Electrical connections Terminal electronics compartment cover terminal assignment see tables below e Service connector see also Page 8 f HART groun...

Page 8: ...sensor correspond to the standard versions Please refer to the Technical Information for these dimensions Note Associated Technical Information Proline Prosonic Flow 92F TI073D 06 Control drawings En...

Page 9: ...D Proline Prosonic Flow 92F FOUNDATION Fieldbus Table of Contents CSA General warnings 10 Special conditions 10 Installation instructions 10 Approvals 10 Description of the measuring system 10 Device...

Page 10: ...must be included in potential matching see Page 13 The devices may only be used for fluids against which the wetted materials are sufficiently resistant The service connector may not be connected in...

Page 11: ...SEALED Provides intrinsically safe sensor circuits See control drawings 1 5W 4153 Reinach Switzerland 2006 1 2 3 4 6 5 A 7 5P CAL TM 40 C 40 F 150 C 302 F CF3M 1 4404 F316L Materials DN100 4 DIN EN PN...

Page 12: ...40 to 130 40 to 195 40 to 200 40 to 200 40 to 60 40 to 130 40 to 195 40 to 200 40 to 200 Prosonic 92F P H K 40 to 60 40 to 130 40 to 195 40 to 200 40 to 200 Ta Tmed C T6 85 C T5 95 C T4 135 C T3 200 C...

Page 13: ...ndress Hauser max 30 m complies with these values Electrical connections Terminal electronics compartment cover terminal assignment see tables below e Service connector see also Page 14 f HART ground...

Page 14: ...ensor correspond to the standard versions Please refer to the Technical Information for these dimensions Note Associated Technical Information Proline Prosonic Flow 92F TI073D 06 Control drawings Endr...

Page 15: ...Proline Prosonic Flow 92F 1 Endress Hauser 15...

Page 16: ...www endress com worldwide XA00113D 06 EN 13 10 71127791 FM SGML 6 0...

Reviews: