Proline Promass P 300
Hauser
101
Data transfer
Manual
• Transfer of a device configuration to another device using the export function of the specific
operating tool, e.g. with FieldCare, DeviceCare or Web server: to duplicate the configuration or to
store in an archive (e.g. for backup purposes)
• Transmission of the drivers for system integration via Web server, e.g.:
– GSD for PROFIBUS DP
– GSD for PROFIBUS PA
– GSDML for PROFINET
– EDS for EtherNet/IP
– DD for FOUNDATION Fieldbus
Event list
Automatic
• Chronological display of up to 20 event messages in the events list
• If the
Extended HistoROM
application package (order option) is enabled: up to 100 event
messages are displayed in the events list along with a time stamp, plain text description and
remedial measures
• The events list can be exported and displayed via a variety of interfaces and operating tools e.g.
DeviceCare, FieldCare or Web server
Data logging
Manual
If the
Extended HistoROM
application package (order option) is enabled:
• Record up to 1
000 measured values via 1 to 4 channels
• User configurable recording interval
• Record up to 250 measured values via each of the 4 memory channels
• Export the measured value log via a variety of interfaces and operating tools e.g. FieldCare,
DeviceCare or web server
Certificates and approvals
Currently available certificates and approvals can be called up via the product configurator.
CE mark
The device meets the legal requirements of the applicable EU Directives. These are listed in the
corresponding EU Declaration of Conformity along with the standards applied.
Hauser confirms successful testing of the device by affixing to it the CE mark.
C-Tick symbol
The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
Ex approval
The measuring device is certified for use in hazardous areas and the relevant safety instructions are
provided in the separate "Safety Instructions" (XA) document. Reference is made to this document on
the nameplate.
Devices with the order code for "Approval; trans sensor", option BA, BB, BC or BD have
equipment protection level (EPL) Ga/Gb (Zone 0 in the measuring tube).
The separate Ex documentation (XA) containing all the relevant explosion protection data is
available from your Hauser sales center.
ATEX/IECEx
Currently, the following versions for use in hazardous areas are available: