Proline Promass 80H, 83H
8
Hauser
FOUNDATION Fieldbus interface:
• FOUNDATION Fieldbus H1, IEC 61158-2, galvanically isolated
• Data transmission rate: 31.25 kBit/s
• Current consumption: 12 mA
• Permitted supply voltage: 9 to 32 V
• Error current FDE (Fault Disconnection Electronic): 0 mA
• Bus connection with integrated reverse polarity protection
• Signal encoding: Manchester II
• ITK Version 4.01
• Function blocks: 7 x Analog Input, 1 x Digital Output, 1 x PID
• Output data: Mass flow, Volume flow, Corrected volume flow, Density, Reference density, Temperature,
Totalizers 1 to 3
• Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode, Reset totalizer
• Link Master (LM) function is supported
Signal on alarm
Current output:
Failsafe mode selectable (e.g. in accordance with NAMUR Recommendation NE 43)
Pulse/frequency output:
Failsafe mode selectable
Status output (Promass 80):
"Nonconductive" in the event of a fault or if the power supply fails
Relay output (Promass 83):
"Dead" in the event of a fault or if the power supply fails
Load
see "Output signal"
Low flow cut off
Switch points for low flow cut off are selectable.
Galvanic isolation
All circuits for inputs, outputs, and power supply are galvanically isolated from each other.
Switching output
Status output (Promass 80):
Open collector, max. 30 V DC / 250 mA, galvanically isolated.
Configurable for: error messages, Empty Pipe Detection (EPD), flow direction,
limit values.
Relay output (Promass 83):
Normally closed (NC or break) or normally open (NO or make) contacts available (factory setting:
relay 1 = NO, relay 2 = NC), max. 30 V / 0.5 A AC; 60 V / 0.1 A DC, galvanically isolated.