Proline Promag L 400 HART
Commissioning
Hauser
77
Assign limit
Select the process variable for
the limit function.
• Volume flow
• Conductivity
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
Volume flow
Assign flow direction check
Select the process variable for
monitoring the direction of
flow in your process.
• Volume flow
• Mass flow
Volume flow
Assign status
Select the device status for
the switch output.
• Empty pipe detection
• Low flow cut off
Empty pipe detection
Volume flow unit
Select the unit for volume
flow.
Result
The selected unit applies for:
– Outputs
– Low flow cut off
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Conductivity unit
Select the unit for
conductivity.
Result
The selected unit applies for:
– Current output
– Frequency output
– Switching output
– Simulation process
variable
Unit choose list
S/m
Mass flow unit
Select the unit for mass flow.
Result
The selected unit applies for:
– Outputs
– Low flow cut off
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Totalizer unit
Select the unit for the process
variable of the totalizer.
Unit choose list
Depends on country and
nominal diameter
Switch-on value
Enter the measured value for
the switch-on value.
Depends on the process
variable selected
-
Switch-off value
Enter the measured value for
the switch-off value.
Depends on the process
variable selected
-
Switch-on delay
Specify the delay time for
switching on the switch
output.
0.0 to 100.0 s
0.0 s
Switch-off delay
Specify the delay time for
switching off the switch
output.
0.0 to 100.0 s
0.0 s
Failure mode
Specify the output behavior
in the event of a device
alarm.
• Current status
• Open
• Closed
Open
Invert output signal
Invert the output signal.
• No
• Yes
No