Commissioning
Proline Promag L 400 HART
74
Hauser
Assign frequency output
Select the process variable for
the frequency output.
• Off
• Volume flow
• Conductivity
• Mass flow
Off
Volume flow unit
Select the unit for volume
flow.
Result
The selected unit applies for:
– Outputs
– Low flow cut off
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Conductivity unit
Select the unit for
conductivity.
Result
The selected unit applies for:
– Current output
– Frequency output
– Switching output
– Simulation process
variable
Unit choose list
S/m
Mass flow unit
Select the unit for mass flow.
Result
The selected unit applies for:
– Outputs
– Low flow cut off
– Simulation process
variable
Unit choose list
Depends on country and
nominal diameter
Density unit
Select the unit for density.
Result
The selected unit applies for:
Fixed density
Unit choose list
Country-dependent
• kg/l
• g/cc
Fixed density
Enter the fixed value for the
density.
Floating-point number
Country-dependent:
• 1 kg/l
• 1 g/cc
Minimum frequency value
Enter the minimum
frequency value.
0.0 to 1
000.0
0.0 Hz
Maximum frequency value
Enter the maximum
frequency value.
0.0 to 10
000.0 Hz
10
000.0 Hz
Measuring value at
minimum frequency
Enter the measured value at
the minimum frequency.
Depends on the process
variable selected
-
Measuring value at
maximum frequency
Specify the measured value at
maximum frequency.
Depends on the process
variable selected
-
Failure mode
Specify the output behavior
in the event of a device
alarm.
• Actual value
• Defined value
• 0 Hz
0 Hz
Failure frequency
Enter the value for the
frequency output in the
event of a device alarm.
0.0 to 12
500.0 Hz
0.0 Hz
Invert output signal
Invert the output signal.
• No
• Yes
No