Installation
Promag 50
16
Hauser
Inlet and outlet run
If possible, install the sensor upstream from fittings such as valves, T-pieces, elbows, etc. The
following inlet and outlet runs must be observed in order to meet accuracy specifications:
• Inlet run:
5 × DN
• Outlet run:
2 × DN
A0003210
Fig. 12:
Inlet and outlet runs
3.2.4
Vibrations
Secure the piping and the sensor if vibration is severe.
"
Caution!
If vibrations are too severe, we recommend the sensor and transmitter be mounted separately.
Information on resistance to vibration and shock can be found on
A0003208
Fig. 13:
Measures to prevent vibration of the device (L > 10 m (32.8 ft))
5 x DN
³
³
2 x DN
L