Proline Promag 10D
14
Hauser
Mounting kit
The device is centered using the recesses on the sensor. Centering sleeves are also provided depending on the
flange standard or the diameter of the pitch circle.
!
Note!
A mounting kit consisting of mounting bolts, seals, nuts and washers can be ordered separately
(see "Accessories").
A0010714
Mounting the sensor
1
Nut
2
Washer
3
Mounting bolt
4
Centering sleeve
5
Seal
Length of connecting cable
Note the following when mounting the remote version:
• Fix cable run or lay in armored conduit.
!
Note!
Cable movements can falsify the measuring signal especially in the case of low fluid conductivities.
• Route the cable well clear of electrical machines and switching elements.
• If necessary, establish potential equalization between the sensor and transmitter.
• The permitted cable length L
max
is determined by the fluid conductivity. A minimum conductivity of
50
μ
S/cm is needed for all fluids.
A0010715
Permitted length of connecting cable for remote version
– The area shaded gray marks the permitted range
– Length of connecting cable L
max
– Fluid conductivity in [
μ
S/cm]
5
1
2
3
4
[ft]
200
600
0
400
200
100
50
100
200
[m]
[ S/cm]
m
L
max
50
L